{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63F32M500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63F32M500","canonicalUrl":"https://aoctrl.com/schneider/C63F32M500","factsUrl":"https://aoctrl.com/api/mcp/products/C63F32M500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX 630F, MCCB, 3P, 500 A at 65 °C, 40 kA Icu at 240 V AC, MicroLogic 2.3 M electronic trip unit, motor protection.","salesMarkdown":"The Schneider Electric C63F32M500 is a ComPacT NSX 630F moulded-case circuit breaker (MCCB) with a MicroLogic 2.3 M electronic trip unit, rated 500 A at 65 °C. It is designed for motor protection in three-phase AC networks at 50/60 Hz. That gives selectivity headroom for a downstream feeder without cascading upstream. For a motor-protection application that means the breaker matches the full-load current of a large motor or a group of motors fed through a common bus. Motor tripping classes 5, 10, and 20 are selectable, letting you match the breaker's overload curve to the motor's thermal withstand. Class 20 is typical for high-inertia loads like fans or centrifuges; class 5 for pumps that start unloaded. The electronic trip unit also provides local signalling: a flashing green LED indicates the breaker is ready to operate; a red LED at 95 % Ith warns of temperature approaching the set point. IP40 enclosure protection keeps out tools and small debris; IK07 impact resistance handles typical panel-door knocks. Relative humidity range 0...95 % covers non-condensing conditions in unheated electrical rooms.","metaTitle":"C63F32M500 ComPacT NSX 630F Circuit Breaker, 500 A, 40 kA","metaDescription":"C63F32M500 ComPacT NSX 630F MCCB, 500 A at 65 °C, 40 kA Icu at 240 V AC. MicroLogic 2.3 M electronic trip unit, motor protection. EN/IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C63F32M500","Depth (D)":"110 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"255 mm","description":"Circuit breaker ComPacT NSX630F, 36kA at 415VAC, MicroLogic 2.3 M trip unit 500A, 3 poles 3d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.3 M","Number of slots":"6 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"45 mm","Local signalling":"Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"500 A at 65 °C","Breaking capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX630F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"500 A at 65 °C","Downside connection":"Front","Motor tripping class":"20 10 5","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical durability":"15000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"39.7 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Complementary motor protection":"Phase unbalance","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"250...500 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"5...13 x Ir","[Ii] instantaneous protection pick-up adjustment range":"6500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,057.12","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/23232e06299f0d11b177f3eebef1c796.pdf","sourceUrl":"https://www.se.com/ae/en/product/C63F32M500/circuit-breaker-compact-nsx630f-36ka-at-415vac-micrologic-2-3-m-trip-unit-500a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the breaking capacity of C63F32M500 at 415 V?","answer":"The C63F32M500 has a breaking capacity of 36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2."},{"question":"Is C63F32M500 suitable for motor protection?","answer":"Yes, the C63F32M500 is designed for motor protection with a MicroLogic 2.3 M electronic trip unit offering selectable motor tripping classes 5, 10, and 20."},{"question":"What standards does C63F32M500 comply with?","answer":"The C63F32M500 complies with EN/IEC 60947-2 and UL 60947-4-1."},{"question":"What is the rated current of C63F32M500?","answer":"The C63F32M500 has a trip unit rating of 500 A at 65 °C."},{"question":"Where can I buy C63F32M500?","answer":"The C63F32M500 is available to order through independent distribution. Submit an RFQ for current pricing and availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63F32M500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63F32M500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}