{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63F42D630","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63F42D630","canonicalUrl":"https://aoctrl.com/schneider/C63F42D630","factsUrl":"https://aoctrl.com/api/mcp/products/C63F42D630","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX NSX630F, 630 A, 40 kA Icu at 240 V AC, 4 poles, MicroLogic 2.3 electronic trip unit, IP40.","salesMarkdown":"The Schneider Electric C63F42D630 is a ComPacT NSX630F moulded-case circuit breaker rated 630 A at 40 °C, with a MicroLogic 2.3 electronic trip unit providing overload (L), short-time short-circuit (So), and instantaneous (I) protection per EN/IEC 60947-2. The 4-pole (4P) configuration with neutral on the left suits distribution panels where full phase-plus-neutral isolation is required. The MicroLogic 2.3 electronic trip unit lets you adjust the long-time pickup and delay, short-time pickup and delay, and instantaneous threshold — not a fixed thermal-magnetic, so you can fine-tune coordination with downstream devices. If your available fault current exceeds that, step to the 'H' or 'L' version in the same frame. Front connections top and bottom, 45 mm pole pitch — standard for panel busbar systems. Overall footprint 255 mm high × 185 mm wide × 110 mm deep. Six accessory slots accept shunt trips, auxiliary contacts, motor mechanisms, or communication modules without increasing the breaker width.","metaTitle":"Schneider Electric C63F42D630 ComPacT NSX630F, 630A, 40kA, 4","metaDescription":"Schneider Electric C63F42D630 ComPacT NSX630F circuit breaker, 630A at 40°C, 40kA Icu at 240V AC, MicroLogic 2.3 trip unit, 4 poles. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C63F42D630","Depth (D)":"110 mm","Standards":"EN/IEC 60947-2","Width (W)":"185 mm","Height (H)":"255 mm","description":"Circuit breaker ComPacT NSX630F, 36kA at 415VAC, MicroLogic 2.3 trip unit 630A, 4 poles 4d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.3","Number of slots":"6 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"45 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"630 A at 40 °C","Breaking capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX630F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"630 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical durability":"15000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)","Power dissipation per pole":"39.7 W","Protected poles description":"4D 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"250...630 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"6900 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,176.86","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/223e0f7b991a3bb857e296b8a7d3a768.pdf","sourceUrl":"https://www.se.com/ae/en/product/C63F42D630/circuit-breaker-compact-nsx630f-36ka-at-415vac-micrologic-2-3-trip-unit-630a-4-poles-4d/"},"ai":{"faq":[{"question":"What is C63F42D630's breaking capacity at 415 V AC?","answer":"36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2."},{"question":"What trip unit does C63F42D630 use?","answer":"MicroLogic 2.3 electronic trip unit with L (long-time), So (short-time with fixed delay), and I (instantaneous) protection."},{"question":"Where can I buy C63F42D630?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63F42D630","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63F42D630 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}