{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63F44V570","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63F44V570","canonicalUrl":"https://aoctrl.com/schneider/C63F44V570","factsUrl":"https://aoctrl.com/api/mcp/products/C63F44V570","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX630F, MCCB, 570 A, 4P, MicroLogic 4.3 electronic trip unit, 36 kA at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"## Integrator note — ComPacT NSX630F, 570 A, 4P The C63F44V570 is a Schneider Electric ComPacT NSX630F moulded-case circuit breaker with a 570 A electronic trip unit (MicroLogic 4.3) at 40 °C, four poles, and an F breaking-capacity code — 36 kA Icu at 415 V AC per IEC 60947-2. ## Breaking capacity — what the F code means The F breaking-capacity code gives 36 kA Icu at 380/415 V AC and 40 kA at 220/240 V AC. At 440 V it drops to 30 kA; at 525 V to 20 kA; at 690 V to 10 kA. That's the full interrupting rating per IEC 60947-2 — the breaker can clear a fault at those levels and still be reclosed. For UL 60947-4-1 applications (motor-circuit protectors), the same breaker carries 85 kA Icu at 240 V AC, 35 kA at 480 V, and 20 kA at 600 V. If your panel is UL-listed, use those numbers for the SCCR calculation. Backplate-mounted, flat on the back, horizontal or vertical orientation. The 4-pole unit is 185 mm wide, 255 mm high, 110 mm deep — fits a standard distribution panel footprint. Front connections top and bottom; neutral on the left. Overvoltage category IV — suitable for main incoming supply. Ambient humidity 0–95 % non-condensing; altitude up to 2000 m without derating, 2000–5000 m with derating.","metaTitle":"Schneider Electric C63F44V570 ComPacT NSX630F MCCB, 570 A, 4","metaDescription":"Schneider Electric C63F44V570 ComPacT NSX630F MCCB, 570 A rated at 40 °C, 4 poles, MicroLogic 4.3 electronic trip unit, 36 kA at 415 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"110 mm","Standards":"EN/IEC 60947-2","Width (W)":"185 mm","Height (H)":"255 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.3","Number of slots":"6 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"45 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"570 A at 40 °C","Breaking capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX630F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"570 A at 40 °C","Downside connection":"Front","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical durability":"15000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)","Power dissipation per pole":"55.6 W N 55.6 W L1 and L3 47.6 W L2","Protected poles description":"4D 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"250...570 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"6900 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"300 mA 500 mA 1 A 3 A 5 A 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,486.39 – $5,951.34","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/453988e0d9b875377b986cc36d7ec09b.pdf","sourceUrl":"https://www.se.com/id/en/product/C63F44V570/circuit-breaker-compact-nsx630f-36ka-at-415vac-micrologic-4-3-vigi-trip-unit-570a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63F44V570/alternatives.json"},"ai":{"faq":[{"question":"What is C63F44V570's listed range and series?","answer":"It belongs to the Schneider Electric ComPacT range, product name ComPacT NSX, device short name NSX630F."},{"question":"What compliance documentation does Schneider Electric provide for C63F44V570?","answer":"The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1 standards. Pollution degree 3 per IEC 60664-1, overvoltage category IV, IP40, IK07. No RoHS/REACH declarations are in this evidence, but standard Schneider Electric compliance documentation applies."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63F44V570","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63F44V570 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}