{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63F47E570","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63F47E570","canonicalUrl":"https://aoctrl.com/schneider/C63F47E570","factsUrl":"https://aoctrl.com/api/mcp/products/C63F47E570","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX630F, molded case circuit breaker, 570 A, 4P, MicroLogic 7.3 E electronic trip unit, 36 kA at 415 V AC.","salesMarkdown":"The Schneider Electric C63F47E570 is a ComPacT NSX630F molded case circuit breaker rated 570 A at 40 °C, 4 poles, with a MicroLogic 7.3 E electronic trip unit. This is the part that sits in the main distribution board or a large motor control center feeder — the one you spec when you need LSI protection plus earth-leakage (R) in a single device, no separate RCD needed. The 570 A rating is the continuous current at 40 °C with the MicroLogic 7.3 E — that's the frame size you pick for a 400–500 kVA transformer secondary or a bank of large drives. Breaking capacity runs from 40 kA at 240 V AC down to 10 kA at 690 V AC per IEC 60947-2, and 85 kA at 240 V AC per UL 60947-4-1. For a 480 V AC plant, the 35 kA Icu (UL) gives comfortable headroom above the typical 18–25 kA available fault current at a secondary switchboard. If you're coordinating downstream, the Category A utilization class means it's not intended for motor-starting duty on its own — pair it with a contactor for motor circuits. That means it's suitable for the main panel where transient overvoltages are highest. ## Deployment and mounting The 255 mm height, 185 mm width, and 110 mm depth fit standard switchboard cubicle compartments. Front connections both top and bottom; neutral on the left (4-pole unit). Accepts horizontal or vertical mounting, flat on the backplate. Six accessory slots for communication modules, auxiliary contacts, shunt trips, or under-voltage releases. The MicroLogic 7.3 E itself logs time-stamped events, energy metering, and power quality data — useful for a plant that tracks energy per panel without a separate power meter.","metaTitle":"Schneider Electric C63F47E570 ComPacT NSX630F, 570A, 4P, Mic","metaDescription":"Schneider Electric C63F47E570 ComPacT NSX630F molded case circuit breaker, 570 A rated current, 4 poles, MicroLogic 7.3 E electronic trip unit with earth-leakage protection. 36 kA","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"110 mm","Standards":"EN/IEC 60947-2","Width (W)":"185 mm","Height (H)":"255 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 7.3 E","Number of slots":"6 slot(s)","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"45 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"570 A at 40 °C","Breaking capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX630F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"570 A at 40 °C","Downside connection":"Front","Type of measurement":"Energy meter","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Time-stamped histories and event tables Maintenance indicators Instantaneous and demand values Maximeters/minimeters Protection and alarm settings Power quality Energy metering Demand current and power","Electrical durability":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical durability":"15000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)","Power dissipation per pole":"55.6 W N 55.6 W L1 and L3 47.6 W L2","Protected poles description":"4D 3D + OSN 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"15...400 s at 1.5 x Ir 0.5...16 s at 6 x Ir 0.35...11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","[Tsd] Short-Time Delay Adjustment Range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Long-time protection delay adjustment type tr":"Adjustable","Short-time protection delay adjustment type tsd":"Adjustable","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"250...570 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1.5...12 x In","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"300 mA 500 mA 1 A 3 A 5 A 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$3,080.16","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e13a0b7ee7ed005fa7cb81a980f704b1.pdf","sourceUrl":"https://www.se.com/ae/en/product/C63F47E570/circuit-breaker-compact-nsx630f-36ka-at-415vac-micrologic-7-3-e-vigi-trip-unit-570a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63F47E570/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C63F47E570 at 415 V?","answer":"The C63F47E570 has a breaking capacity of 36 kA Icu at 380/415 V AC per IEC 60947-2. This is the F capacity code for the NSX630F frame."},{"question":"What protection functions does the MicroLogic 7.3 E trip unit provide?","answer":"The MicroLogic 7.3 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection. All settings are adjustable via the front LCD display."},{"question":"Where can I buy C63F47E570?","answer":"The C63F47E570 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63F47E570","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63F47E570 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}