{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63L4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63L4","canonicalUrl":"https://aoctrl.com/schneider/C63L4","factsUrl":"https://aoctrl.com/api/mcp/products/C63L4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX630L basic frame, C63L4, 630 A at 40 °C, 150 kA Icu at 415 V AC, 4 poles, toggle control, fixed mount.","salesMarkdown":"## What this basic frame is and where it fits The Schneider Electric C63L4 is a ComPacT NSX630L basic frame — a 4-pole, 630 A at 40 °C air circuit breaker without a trip unit or protection module installed. It carries a 150 kA Icu at 415 V AC breaking capacity (code L), making it a high-interrupt choice for distribution switchboards where fault levels run deep. The frame is rated for isolation per EN/IEC 60947-2 and carries a Class II shock protection front face, so it can serve as a visible disconnect in a panel without needing an additional isolator upstream. ## What the ratings mean for a panel build The 630 A continuous rating at 40 °C ambient sets the thermal limit for the bus bars and cable connections on the load side. The 150 kA Icu at 415 V AC means this frame can safely interrupt a fault up to that level without self-destructing — critical for high-fault installations like large motor control centers or transformer secondaries. The Ics (service breaking capacity) at the same voltage is also 150 kA, so after clearing a fault at full rating the breaker can be reclosed and carry load again, not just be swapped out. The 8 kV impulse withstand (Uimp) and overvoltage category III rating confirm it's built for fixed-installation distribution panels, not plug-in equipment. ## Compliance and documentation The C63L4 is certified to EN/IEC 60947-2 and UL 60947-4-1, covering both the circuit breaker standard and the combination motor-controller standard. Pollution degree 3 per IEC 60664-1 means it's rated for industrial environments with conductive pollution. IP40 front face and IK07 impact resistance handle typical panel conditions. The manufacturer provides a declaration of performance and a CE declaration of conformity with the shipment; RoHS and REACH compliance documentation is included in the technical file.","metaTitle":"Schneider Electric C63L4 ComPacT NSX630L Basic Frame, 630A,","metaDescription":"Schneider Electric C63L4 ComPacT NSX630L basic frame, 630 A at 40 °C, 150 kA Icu at 415 V AC. Current production. Sourced to order against RFQ. EN/IEC 60947-2, UL 60947-4-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"110 mm","Width":"185 mm","Height":"255 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Protection Type":"Without protection","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 8000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2","Mechanical Life Cycles":"15000 cycles conforming to IEC 60947-2","Connection Surface Bottom":"Front","Main Product Or Component Type":"Basic frame","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,053.73 – $3,067.90","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/06ac623e069d9ba627f0421557952e46.pdf","sourceUrl":"https://www.se.com/hk/en/product/C63L4/circuit-breaker-basic-frame-compact-nsx630l-150-ka-at-415-vac-50-60-hz-630-a-without-trip-unit-4-poles/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63L4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63L4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63L4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}