{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63N34V570","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63N34V570","canonicalUrl":"https://aoctrl.com/schneider/C63N34V570","factsUrl":"https://aoctrl.com/api/mcp/products/C63N34V570","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, ComPacT NSX series, earth leakage circuit breaker, C63N34V570, 3P, 570 A at 40 °C, 85 kA Icu at 240 V AC, MicroLogic 4.3 trip unit.","salesMarkdown":"That 570 A is the continuous current the trip unit carries without tripping — sized for a main feeder or large downstream distribution board, not a branch circuit. The 85 kA Icu at 240 V AC (50/60 Hz) is the maximum fault current it can interrupt and still be usable afterward; at 480 V AC that drops to 50 kA Icu, and at 690 V AC to 10 kA Icu. For a 480 V panel with an available fault current of, say, 65 kA, this breaker clears it — but at 690 V you need the higher-rated frame. The MicroLogic 4.3 electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection curves. The earth-leakage is integrated — no external Vigi module needed, which saves a pole width in the panel. ## Deployment context Backplate-mounted in a distribution panel, 140 mm wide × 255 mm high × 110 mm deep. IP40 enclosure protection means it's indoors only — no washdown or outdoor exposure without a secondary enclosure. Overvoltage category IV, utilization category A. Breaking capacities also listed per UL 60947-4-1 at 240 V (85 kA), 480 V (50 kA), and 600 V (20 kA) — relevant for North American installations where UL listing is required.","metaTitle":"Schneider Electric C63N34V570 ComPacT NSX630N, 570 A, 85 kA","metaDescription":"Schneider Electric C63N34V570 ComPacT NSX630N MCCB, 570 A trip unit, 85 kA Icu at 240 V AC, MicroLogic 4.3 electronic trip, earth-leakage protection, EN/IEC 60947-2. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"110 mm","Width":"140 mm","Height":"255 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical Life Cycles":"15000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,212.32 – $5,438.88","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5a7e86401fe6792970f530cfff466142.pdf","sourceUrl":"https://www.se.com/vn/en/product/C63N34V570/circuit-breaker-compact-nsx630n-50ka-415vac-3-poles-micrologic-vigi-4-3-trip-unit-570a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63N34V570/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63N34V570","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63N34V570 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}