{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63R36M500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63R36M500","canonicalUrl":"https://aoctrl.com/schneider/C63R36M500","factsUrl":"https://aoctrl.com/api/mcp/products/C63R36M500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, C63R36M500, NSX630R 3-pole MCCB, 500 A rated, MicroLogic 6.3 E-M electronic trip unit, 200 kA Icu at 415 V AC, motor protection application.","salesMarkdown":"The Schneider Electric C63R36M500 is a ComPacT NSX630R 3-pole moulded-case circuit breaker rated 500 A at 65 °C, fitted with a MicroLogic 6.3 E-M electronic trip unit. The toggle-operated breaker mounts on a backplate, connects front-top and front-bottom, and includes an LCD display for metering and protection settings. The R-code breaking capacity delivers 200 kA Icu at 220/240 V AC and 380/415 V AC, 80 kA at 500 V AC, and 45 kA at 660/690 V AC. The MicroLogic 6.3 E-M trip unit provides L (long-time), So (short-time short-circuit), I (instantaneous), and G (ground-fault) protection. Motor tripping classes 5, 10, 20, and 30 are selectable, so it matches the thermal curve of a 500 A motor circuit — pump, conveyor, compressor — without nuisance tripping on start-up inrush. Front-face connections top and bottom — 45 mm connection pitch — so it fits standard panel busbar layouts. Six accessory slots accommodate shunt trips, auxiliary contacts, or communication modules. The LCD display shows demand current, power, energy metering, time-stamped event logs, and protection settings — no separate panel meter needed for motor load monitoring.","metaTitle":"Schneider C63R36M500 ComPacT NSX 630A 3P MCCB, 200 kA at 415","metaDescription":"Schneider Electric C63R36M500 ComPacT NSX630R MCCB, 3-pole, 500 A MicroLogic 6.3 E-M trip unit, 200 kA breaking capacity at 415 V AC. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"110 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"255 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 6.3 E-M","Number of slots":"6 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Connection pitch":"45 mm","Local signalling":"Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"500 A at 65 °C","Breaking capacity":"200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX630R","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"500 A at 65 °C","Downside connection":"Front","Type of measurement":"Energy meter","Motor tripping class":"5 30 20 10","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Demand current and power Time-stamped histories and event tables Maintenance indicators Maximeters/minimeters Protection and alarm settings Instantaneous and demand values Energy metering Phase sequence Thermal image function Power quality","Electrical durability":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical durability":"15000 cycles","Breaking capacity code":"R 200 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"39.7 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Complementary motor protection":"Stalled rotor Phase unbalance Protracted starting time Underload","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20 720 s at 1.5 x Ir for trip class 30 38 s at 6 x Ir for trip class 30 30 s at 7.2 x Ir for trip class 30","[Uimp] rated impulse withstand voltage":"8 kV","[Ig] ground-fault pick-up adjustment range":"0.6...1 x In for In = 25 A 0.3...1 x In for In = 50 A 0.2...1 x In for In > 50 A Ig enable on/off","Long-time protection delay adjustment type tr":"Adjustable","[tg] Ground-fault time delay adjustment range":"0...0.4 s","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"250...500 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"5...13 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable 5 settings","[Ii] instantaneous protection pick-up adjustment range":"6500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$34.74","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/45d9500e4b73c74d8c46520d74a87cce.pdf","sourceUrl":"https://www.se.com/hk/en/product/C63R36M500/circuit-breaker-compact-nsx630r-200ka-415vac-3-poles-micrologic-6-3em-trip-unit-500a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63R36M500/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C63R36M500 at 415 V?","answer":"200 kA Icu at 380/415 V AC per IEC 60947-2. At 500 V AC it is 80 kA Icu; at 690 V AC it is 45 kA Icu."},{"question":"What does the MicroLogic 6.3 E-M trip unit protect against?","answer":"It provides L (long-time overload), So (short-time short-circuit), I (instantaneous short-circuit), and G (ground-fault) protection. Motor tripping classes 5, 10, 20, and 30 are selectable."},{"question":"Where can I buy C63R36M500?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63R36M500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63R36M500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}