{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63V32M500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63V32M500","canonicalUrl":"https://aoctrl.com/schneider/C63V32M500","factsUrl":"https://aoctrl.com/api/mcp/products/C63V32M500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX circuit breaker, C63V32M500, 3P, 500 A at 65 °C, MicroLogic 2.3 M electronic trip unit, 85 kA Icu at 500 V AC, motor protection application.","salesMarkdown":"## Motor protection breaker with MicroLogic 2.3 M trip unit Its MicroLogic 2.3 M electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves, with selectable motor tripping classes 5, 10, and 20 — matching the thermal characteristics of the motor winding. Breaking capacity hits 85 kA Icu at 500 V AC 50/60 Hz per IEC 60947-2, with 80 kA at 525 V and 75 kA at 690 V. That SCCR headroom means it clears high-fault bolted shorts on a motor branch without upstream coordination issues. Front connections top and bottom simplify bus-bar or cable routing in a panel. IP40 enclosure rating keeps dust out of the trip unit electronics; IK07 impact resistance handles panel-door knocks. Six accessory slots on the front accept auxiliary contacts, shunt trips, or motor operators without increasing panel depth. Operating altitude 0–2000 m without derating, 2000–5000 m with derating. Relative humidity 0–95%.","metaTitle":"C63V32M500 ComPacT NSX 500A 85kA MCCB, Motor Protection","metaDescription":"C63V32M500 ComPacT NSX circuit breaker, 500A at 65°C, 85kA Icu at 500V AC, MicroLogic 2.3 M trip unit, motor protection. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C63V32M500","Depth (D)":"110 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"255 mm","description":"Circuit breaker, ComPacT NSX630HB1, 75kA/690VAC, 3 poles, MicroLogic 2.3M trip unit 500A","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.3 M","Number of slots":"6 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"45 mm","Local signalling":"Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"500 A at 65 °C","Breaking capacity":"85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX630HB1","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"500 A at 65 °C","Downside connection":"Front","Motor tripping class":"20 10 5","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical durability":"15000 cycles","Breaking capacity code":"HB1 75 kA 690 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"39.7 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Complementary motor protection":"Phase unbalance","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"250...500 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"5...13 x Ir","[Ii] instantaneous protection pick-up adjustment range":"6500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b2c9a35ee3e23f56cc044845983c7122.pdf","sourceUrl":"https://www.se.com/au/en/product/C63V32M500/circuit-breaker-compact-nsx630hb1-75ka-690vac-3-poles-micrologic-2-3m-trip-unit-500a/"},"ai":{"faq":[{"question":"What is C63V32M500 used for?","answer":"It is a motor protection circuit breaker — the MicroLogic 2.3 M trip unit is specifically configured for motor branch circuits, with adjustable overload class and short-circuit protection."},{"question":"What breaking capacity does C63V32M500 have?","answer":"85 kA Icu at 500 V AC, 80 kA at 525 V, and 75 kA at 690 V, all per IEC 60947-2."},{"question":"Where can I buy C63V32M500?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63V32M500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63V32M500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}