{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63V36M500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63V36M500","canonicalUrl":"https://aoctrl.com/schneider/C63V36M500","factsUrl":"https://aoctrl.com/api/mcp/products/C63V36M500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C63V36M500, 3P 500 A MCCB with MicroLogic 6.3 E-M electronic trip unit, 85 kA Icu at 500 V AC, motor protection, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C63V36M500 is a ComPacT NSX630HB1 molded-case circuit breaker with a MicroLogic 6.3 E-M electronic trip unit, rated 500 A at 65 °C. It's built for motor-protection duty (device application: motor protection) and carries a 85 kA Icu breaking capacity at 500 V AC 50/60 Hz per EN/IEC 60947-2. The 3-pole unit (3P) uses a toggle control and an LCD display for local signalling — a flashing green LED for ready status, a red LED at 95 % Ith for overtemperature. The electronic trip unit provides L (long-time overload), So (short-time short-circuit), I (instantaneous), and G (ground-fault) protection, with motor tripping classes 5, 10, 20, and 30 selectable. At 690 V AC the Icu drops to 75 kA, still substantial for industrial feeders. Mechanical durability is 15000 cycles. That's enough for a motor-starting application where the breaker operates infrequently (a few cycles per day), not for a switching duty that cycles hourly. Upside and downside connections are front-facing, so it panels into a dead-front switchboard without rear access. Connection pitch is 45 mm. Overvoltage category III suits it for fixed-installation distribution panels. Operating altitude is 0-2000 m without derating, 2000-5000 m with derating.","metaTitle":"Schneider Electric C63V36M500 ComPacT NSX 500 A, 85 kA ICu,","metaDescription":"Schneider Electric C63V36M500 ComPacT NSX circuit breaker, 500 A, 85 kA Icu at 500 V AC, MicroLogic 6.3 E-M trip unit. Motor protection, EN/IEC 60947-2. Active production, availabl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"110 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"255 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 6.3 E-M","Number of slots":"6 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Connection pitch":"45 mm","Local signalling":"Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"500 A at 65 °C","Breaking capacity":"85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX630HB1","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"500 A at 65 °C","Downside connection":"Front","Type of measurement":"Energy meter","Motor tripping class":"20 5 30 10","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Protection and alarm settings Demand current and power Power quality Thermal image function Energy metering Time-stamped histories and event tables Maximeters/minimeters Instantaneous and demand values Phase sequence Maintenance indicators","Electrical durability":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical durability":"15000 cycles","Breaking capacity code":"HB1 75 kA 690 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"39.7 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Complementary motor protection":"Protracted starting time Stalled rotor Phase unbalance Underload","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20 720 s at 1.5 x Ir for trip class 30 38 s at 6 x Ir for trip class 30 30 s at 7.2 x Ir for trip class 30","[Uimp] rated impulse withstand voltage":"8 kV","[Ig] ground-fault pick-up adjustment range":"0.6...1 x In for In = 25 A 0.3...1 x In for In = 50 A 0.2...1 x In for In > 50 A Ig enable on/off","Long-time protection delay adjustment type tr":"Adjustable","[tg] Ground-fault time delay adjustment range":"0...0.4 s","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"250...500 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"5...13 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable 5 settings","[Ii] instantaneous protection pick-up adjustment range":"6500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$19.85","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b8c4388647d3806caa01a62b4ef413c9.pdf","sourceUrl":"https://www.se.com/ae/en/product/C63V36M500/circuit-breaker-compact-nsx630hb1-75ka-at-690vac-micrologic-6-3-em-trip-unit-500a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63V36M500/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C63V36M500?","answer":"85 kA Icu at 500 V AC 50/60 Hz per IEC 60947-2, 80 kA at 525 V, and 75 kA at 660/690 V."},{"question":"What trip unit does C63V36M500 use?","answer":"It uses a MicroLogic 6.3 E-M electronic trip unit, providing L (long-time overload), So (short-time short-circuit), I (instantaneous), and G (ground-fault) protection, with motor tripping classes 5, 10, 20, and 30."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63V36M500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63V36M500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}