{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63V36M500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63V36M500","canonicalUrl":"https://aoctrl.com/schneider/C63V36M500","factsUrl":"https://aoctrl.com/api/mcp/products/C63V36M500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C63V36M500, 3P 500 A MCCB with MicroLogic 6.3 E-M electronic trip unit, 85 kA Icu at 500 V AC, motor protection, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C63V36M500 is a ComPacT NSX630HB1 molded-case circuit breaker with a MicroLogic 6.3 E-M electronic trip unit, rated 500 A at 65 °C. It's built for motor-protection duty (device application: motor protection) and carries a 85 kA Icu breaking capacity at 500 V AC 50/60 Hz per EN/IEC 60947-2. The 3-pole unit (3P) uses a toggle control and an LCD display for local signalling — a flashing green LED for ready status, a red LED at 95 % Ith for overtemperature. The electronic trip unit provides L (long-time overload), So (short-time short-circuit), I (instantaneous), and G (ground-fault) protection, with motor tripping classes 5, 10, 20, and 30 selectable. At 690 V AC the Icu drops to 75 kA, still substantial for industrial feeders. Mechanical durability is 15000 cycles. That's enough for a motor-starting application where the breaker operates infrequently (a few cycles per day), not for a switching duty that cycles hourly. Upside and downside connections are front-facing, so it panels into a dead-front switchboard without rear access. Connection pitch is 45 mm. Overvoltage category III suits it for fixed-installation distribution panels. Operating altitude is 0-2000 m without derating, 2000-5000 m with derating.","metaTitle":"Schneider Electric C63V36M500 ComPacT NSX 500 A, 85 kA ICu,","metaDescription":"Schneider Electric C63V36M500 ComPacT NSX circuit breaker, 500 A, 85 kA Icu at 500 V AC, MicroLogic 6.3 E-M trip unit. Motor protection, EN/IEC 60947-2. Active production, availabl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"110 mm","Width":"140 mm","Height":"255 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical Life Cycles":"15000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$19.85","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b8c4388647d3806caa01a62b4ef413c9.pdf","sourceUrl":"https://www.se.com/ae/en/product/C63V36M500/circuit-breaker-compact-nsx630hb1-75ka-at-690vac-micrologic-6-3-em-trip-unit-500a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63V36M500/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63V36M500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63V36M500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}