{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63W36E630","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63W36E630","canonicalUrl":"https://aoctrl.com/schneider/C63W36E630","factsUrl":"https://aoctrl.com/api/mcp/products/C63W36E630","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX630HB2, 3P, 630 A, 100 kA Icu at 690 V AC, MicroLogic 6.3 E electronic trip unit, EN/IEC 60947-2.","salesMarkdown":"Above that, the electronic trip unit thermally models the conductor heating with a 20-minute thermal memory before and after tripping — so a reclose after a fault sees the residual heat and shortens the next trip time. The 3-pole configuration with front connections and 45 mm pitch fits standard backplate mounting, horizontal or vertical. ## Integration notes Mounts on a backplate, flat on the back, in either horizontal or vertical orientation. Front connections on both line and load sides; the 45 mm pole pitch matches standard busbar systems. IP40 enclosure protection means it's suited for indoor panel installation, not washdown environments. The toggle control and LCD display give local status and trip indication without opening the door.","metaTitle":"Schneider Electric C63W36E630 ComPacT NSX 630A 3P MCCB, 100","metaDescription":"Schneider Electric C63W36E630 ComPacT NSX 630A 3P MCCB with MicroLogic 6.3 E trip unit. 100 kA Icu at 690 V AC, EN/IEC 60947-2. Current lifecycle stage, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"110 mm","Width":"140 mm","Height":"255 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical Life Cycles":"15000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$20.19","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/80ff03ee4c4f4934bd38fe621519f778.pdf","sourceUrl":"https://www.se.com/au/en/product/C63W36E630/circuit-breaker-compact-nsx630hb2-100ka-690vac-3-poles-micrologic-6-3e-trip-unit-630a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63W36E630/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63W36E630","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63W36E630 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}