{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C63W36M500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C63W36M500","canonicalUrl":"https://aoctrl.com/schneider/C63W36M500","factsUrl":"https://aoctrl.com/api/mcp/products/C63W36M500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX630HB2, C63W36M500, 500 A, 100 kA Icu at 500 V AC, MicroLogic 6.3 E-M trip unit, 3P, motor protection.","salesMarkdown":"The Schneider Electric C63W36M500 is a ComPacT NSX motor-protection circuit breaker with a MicroLogic 6.3 E-M electronic trip unit, rated 500 A at 65 °C and delivering 100 kA Icu at 500 V AC (50/60 Hz) per IEC 60947-2. The E-M trip curve offers L (long-time overload), So (short-time short-circuit), I (instantaneous), and G (ground-fault) protection, with motor tripping classes 5, 10, 20, and 30 selectable. That means you can match the trip class to the motor start profile — a class 10 for a standard pump, class 20 for a high-inertia fan. The 3-pole design with front connections (upside and downside) simplifies bus-bar or cable routing in a backplate-mounted panel. The 140 mm width, 255 mm height, and 110 mm depth fit standard MCC bucket cutouts. The LCD display on the MicroLogic 6.3 E-M shows energy metering, demand current, power, phase sequence, and time-stamped event logs — useful for commissioning without a separate power meter. The toggle control and flashing green/red LEDs provide local status at a glance. ## Durability and environmental Rated for 15,000 mechanical cycles and 8,000 electrical cycles at 440 V at half rated current (In/2), or 4,000 cycles at full In. At 690 V, electrical durability is 6,000 cycles at In/2 and 2,000 at In. Operating altitude is 0–2000 m without derating, 2000–5000 m with derating.","metaTitle":"Schneider Electric C63W36M500 ComPacT NSX 500 A, 100 kA Icu,","metaDescription":"Schneider Electric C63W36M500 ComPacT NSX motor-protection circuit breaker, 500 A rated current, 100 kA Icu at 500 V AC, MicroLogic 6.3 E-M trip unit. Sourced to order; RFQ for cur","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"110 mm","Width":"140 mm","Height":"255 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"45 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In","Mechanical Life Cycles":"15000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,748.21","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9fdd6e9cc5d3dd2f75d0dfca5b912f1d.pdf","sourceUrl":"https://www.se.com/be/en/product/C63W36M500/circuit-breaker-compact-nsx630hb2-100ka-690vac-3-poles-micrologic-6-3em-trip-unit-500a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C63W36M500/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C63W36M500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C63W36M500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}