{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CAD326EDS135","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CAD326EDS135","canonicalUrl":"https://aoctrl.com/schneider/CAD326EDS135","factsUrl":"https://aoctrl.com/api/mcp/products/CAD326EDS135","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys CAD326EDS135 DC-operated control relay, 48 VDC coil, 3NO-2NC contact configuration, 10 A at 600 VAC / 2.5 A at 600 VDC, 5-pole, 35 mm DIN rail mount, IP2X.","salesMarkdown":"The CAD326EDS135: The 48 VDC coil makes this a DC-operated control relay, not an AC contactor — it pulls in on a DC control bus, common in battery-backed or PLC-driven panels where AC coil hum is undesirable. Contact configuration is 3 normally-open and 2 normally-closed poles, giving you five isolated switching paths. The mixed NO/NC arrangement suits interlocking circuits where you need both a seal-in and a safety-break contact from the same relay. Rated 10 A at 600 VAC and 2.5 A at 600 VDC — the DC rating is the limiting factor for inductive loads; at 48 VDC the contact can switch more current than the 600 VDC rating suggests, but the arc-quenching gap is sized for the 600 VDC ceiling. Compliant with IEC 60947-5-1 and EN 60947-5, the control-circuit switching standard that governs contact reliability and electrical endurance for industrial relay outputs. ## DIN-rail fit and panel integration IP2X enclosure provides finger-safe protection against solid objects >12.5 mm but is not sealed against moisture — install inside a cabinet with at least IP54 rating if the environment has condensation or washdown. Ring-tongue terminals require a crimp ring lug on each wire — plan for ring-tongue terminations in your panel bill of materials; they give a vibration-resistant connection compared to ferrules on a screw clamp. ## Lifecycle and sourcing — current production, no replacement watch needed Part of the TeSys series, Schneider's broadest control-relay family, which means compatible accessories (socket bases, clip-on suppressors, mechanical interlocks) are widely available and will remain so.","metaTitle":"Schneider CAD326EDS135 DC Relay, 48 VDC Coil, 3NO-2NC, 10 A","metaDescription":"Schneider Electric CAD326EDS135 TeSys DC-operated control relay, 48 VDC coil, 3NO-2NC contacts, 10 A at 600 VAC. UL/CSA/CE. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"UPC":"78590144858","Type":"DC OPERATED","Model":"CAD","title":"CAD326EDS135","Approval":"UL, CSA, CE","Category":"Monitoring Relays &amp; Accessories","Mounting":"35 MM DIN 3 TRACK","Enclosure":"IP2X","Brand Name":"TeSys[R]","description":"Square D CAD326EDS135 Relay 600V 10Amp W/O Suppressor|SQUARE D CAD326EDS135: RELAY 600V 10AMP W/O SUPPRESSOR","Coil Voltage":"48 VDC","Contact Type":"FIXED","Sub-Category":"Control Relay","UPC 12 Digit":"785901448587","Terminal Type":"RING TONGUE","Number of Poles":"5","Prop 65 warning":"WARNING: THIS PRODUCT CAN EXPOSE YOU TO CHEMICALS INCLUDING: ANTIMONY OXIDE &amp; ANTIMONY TRIOXIDE, WHICH IS KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER. FOR MORE INFORMATION GO TO WWW.P65WARNINGS.CA.GOV","lifecycle_stage":"current","Manufacturer Brand":"Square D Co.","Applicable Standard":"BS 4794, EN 60947-5, IEC 60947-5-1, NFC 63-140, VDE 0660","Product Description":"Square D CAD326EDS135 Relay 600V 10Amp W/O Suppressor","Contact Configuration":"3NO-2NC","Additional Information":"OPERATING TEMPERATURE -40 TO 158 DEG F","Contact Current Rating":"10 AMPERE AT 600 VAC, 2.5 AMPERE AT 600 VDC","Contact Voltage Rating":"600 VAC/VDC","Full Technical Description":"DC Operated Type; 3NO-2NC Contact Configuration; UL, CSA, CE Approval; BS 4794, En 60947-5, IEC 60947-5-1, Nfc 63-140, VDE 0660 Applicable Standard; 35 mm DIN 3 Track Mounting; IP2X Enclosure; 5 Pole(S); Ring Tongue Terminal Type; 48 VDC Coil Voltage; Fixed Contact Type; 10 Ampere at 600 VAC, 2.5 Ampere at 600 VDC Contact Current Rating; 600 VAC/VDC Contact Voltage Rating; TESYS[R] Brand; Operating Temperature -40 to 158 Deg F; CAD Model","Proposition 65 Warning (CA)":"WARNING: This product can expose you to chemicals including: Antimony oxide &amp; Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.p65warnings.ca.gov"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$114.59 – $245.35","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/73528907832468d71620b4e504b494ce.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What compliance documentation does Schneider Electric provide for CAD326EDS135?","answer":"The relay carries UL, CSA, and CE approvals, and is designed to meet BS 4794, EN 60947-5, IEC 60947-5-1, NFC 63-140, and VDE 0660. A Proposition 65 warning for antimony oxide/trioxide is on file. RoHS and REACH compliance documentation is available from Schneider's compliance portal for the TeSys series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CAD326EDS135","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CAD326EDS135 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}