{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CAD326U7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CAD326U7","canonicalUrl":"https://aoctrl.com/schneider/CAD326U7","factsUrl":"https://aoctrl.com/api/mcp/products/CAD326U7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider CAD326U7 Solid State Overload Relays — now discontinued, supplied from remaining surplus and broker stock.","salesMarkdown":"## Overview The CAD326U7 is a Schneider TeSys Deca control relay with a 3NO-2NC contact arrangement, a 240 V AC standard coil, and a switching current rating of 10 A across AC-14, AC-15, and DC-13 utilization categories. It carries global certifications including UL, CSA, CCC, CE, UKCA, and EAC, and is sealed to IP2X on the front face per VDE 0106. An RFQ confirms current availability for line-down or last-time-buy needs. Compared to the CAD50GD, the CAD326U7 uses a 240 V AC coil (vs 125 V DC) and a 3NO-2NC contact form (vs 5 NO), making the CAD50GD the right pick when a 5-NO DC-operated relay is required.","metaTitle":"Schneider CAD326U7 TeSys Deca control relay, 3NO-2NC, 240 V AC, 10 A","metaDescription":"Schneider CAD326U7 TeSys Deca control relay: 3NO-2NC contacts, 240 V AC coil, 10 A switching, AC-14/AC-15/DC-13, UL/CSA/CCC/CE. Discontinued; source via surplus.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"3.3 in (84 mm)","Range":"TeSys TeSys Deca","Width":"1.8 in (45 mm)","Height":"3.03 in (77 mm)","Category":"US10I1222371","Standards":"EN/IEC 60947-5-1 GB/T 14048.5 UL 60947-5-1 CSA C22.2 No 60947-5-1 JIS C8201-5-1","Product name":"TeSys CAD","lifecycle_stage":"current","Device short name":"CAD","Operating altitude":"0...9842.52 ft (0...3000 m)","Protective treatment":"TH IEC 60068","Utilisation category":"AC-14 AC-15 DC-13","Contactor application":"Control circuit","Mechanical robustness":"Shocks control relay open10 Gn for 11 ms IEC 60068-2-27 Shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 Vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 Vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6","Nbr. of units in pkg.":"1","IP degree of protection":"IP2X front face VDE 0106","Pole contact composition":"3 NO + 2 NC","Product or Component Type":"Control relay","[Ue] rated operational voltage":"10 MOhm","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient air temperature for operation":"-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$38.10","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/73528907832468d71620b4e504b494ce.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/CAD326U7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CAD326U7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CAD326U7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}