{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CAD32AU7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CAD32AU7","canonicalUrl":"https://aoctrl.com/schneider/CAD32AU7","factsUrl":"https://aoctrl.com/api/mcp/products/CAD32AU7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca control relay, CAD32AU7, 3NO+2NC, <=690V, 240V AC standard coil, snap-in terminals, depth 93 mm.","salesMarkdown":"The CAD32AU7: The utilisation categories — AC-15, AC-14, and DC-13 — define the switching capability for control circuits. AC-15 covers solenoid loads (the typical contactor coil or valve), AC-14 covers electromagnetic loads with low inrush, and DC-13 covers DC solenoids. For a control relay, these are the right duty classes: they tell you the relay can switch the inductive loads found in a panel, not just resistive ones. The 3NO+2NC contact arrangement gives you three make contacts for pilot devices and two break contacts for interlocks or status feedback, which is the standard pattern for a control relay in a motor starter or safety circuit. This is a panel-interior part, not a field-mounted device. The TH protective treatment conforming to IEC 60068 means it's treated against tropical humidity, which is useful for non-conditioned plant rooms or shipping containers. Storage range is -60 to 80 °C. The relay withstands 10 Gn shocks for 11 ms in the open state and 15 Gn when closed, and vibration at 2 Gn (open) and 4 Gn (closed) across 5 to 300 Hz. That's solid for industrial panel vibration from contactors or drives on the same rail. Operating altitude is 0 to 3000 m — no derating needed at typical plant elevations, but above 2000 m you'd check the dielectric withstand per IEC 60947-1.","metaTitle":"Schneider Electric CAD32AU7 TeSys Control Relay, 3NO+2NC, 24","metaDescription":"Schneider Electric CAD32AU7 TeSys Deca control relay, 3NO+2NC contacts, 240V AC standard coil, snap-in terminals. Active production. Complies with EN/IEC 60947-5-1, UL 60947-5-1, C","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"93 mm","Range":"TeSys","Width":"45 mm","title":"CAD32AU7","Height":"107 mm","Standards":"EN/IEC 60947-5-1 UL 60947-5-1 CSA C22.2 No 60947-5-1 GB/T 14048.5 JIS C8201-5-1","description":"Control relay, TeSys Deca, 3NO+2NC, <=690V, 240V AC standard coil, snap-in terminals","Product name":"TeSys CAD","lifecycle_stage":"current","Device short name":"CAD","Operating altitude":"0...3000 m","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-15 AC-14 DC-13","Contactor application":"Control circuit","Mechanical robustness":"Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP2X front face conforming to VDE 0106","Pole contact composition":"3 NO + 2 NC","Product or component type":"Control relay","[Ue] rated operational voltage":"10 MOhm","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-40...60 °C 60...70 °C with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2822afdcfaf901ff6fe9bda770baa5f4.pdf","sourceUrl":"https://www.se.com/be/en/product/CAD32AU7/control-relay-tesys-deca-3no+2nc-690v-240v-ac-standard-coil-snapin-terminals/"},"ai":{"faq":[{"question":"What standards does CAD32AU7 comply with?","answer":"It complies with EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, and JIS C8201-5-1. These cover control circuit devices for industrial switching applications."},{"question":"What is the contact configuration of CAD32AU7?","answer":"The relay has 3 normally open and 2 normally closed pole contacts (3NO+2NC), which is a standard arrangement for a control relay handling both make and break functions in a motor control circuit."},{"question":"What is the depth of CAD32AU7?","answer":"The depth is 93 mm. Combined with a width of 45 mm and height of 107 mm, it fits a standard DIN-rail footprint for control relays in the TeSys range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CAD32AU7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CAD32AU7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}