{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CAD506FDS207","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CAD506FDS207","canonicalUrl":"https://aoctrl.com/schneider/CAD506FDS207","factsUrl":"https://aoctrl.com/api/mcp/products/CAD506FDS207","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D control relay, CAD506FDS207, 5 NO contacts, 690 V rated operational voltage, 110 V DC standard coil, IP20 front face.","salesMarkdown":"## Part identity and sourcing status The CAD506FDS207: Rated operational voltage is 690 V, and it carries utilisation categories AC-15, DC-13, and AC-14 — meaning it's rated for switching solenoid loads, electromagnetic clutches, and contactor coils in control circuits. The 5 NO contact arrangement gives you five independent normally-open circuits, all switching together. That's useful for distributing a single control signal to multiple loads — think contactor coils, pilot lights, or PLC inputs that need simultaneous closure. This relay lives inside an enclosure — it's not for washdown areas or outdoor panels without a cover. The TH protective treatment per IEC 60068 means it's been tested for tropical conditions — humidity and fungus resistance — so it's fine for non-condensing damp environments. Mechanical robustness specs: the relay stays closed under 15 Gn shock for 11 ms, open under 10 Gn. Vibration resistance is 4 Gn closed, 2 Gn open across 5-300 Hz. That's enough for most fixed industrial machinery; for high-vibration applications like mobile equipment, you'd want to check the mounting orientation. ## Physical integration Dimensions are 77 mm high, 45 mm wide, 93 mm deep.","metaTitle":"TeSys CAD506FDS207 Control Relay, 5 NO, 110 VDC Coil","metaDescription":"Active TeSys D control relay, 5 NO contacts, 690 V rated, 110 V DC coil. Standards: EN/IEC 60947, UL 60947-4-1, CSA. IP20 front face. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Control Accessories"],"specifications":{"Depth":"93 mm","Range":"TeSys","Width":"45 mm","title":"CAD506FDS207","Height":"77 mm","Standards":"EN 45545: R22 HL3 EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1","description":"TeSys D control relay - 5 NO - 690 V - 110 V DC standard coil","Product name":"TeSys CAD","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Flame retardance":"V0 conforming to UL 94","Device short name":"CAD","Operating altitude":"0...3000 m","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-15 DC-13 AC-14","Contactor application":"Control circuit","Mechanical robustness":"Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6","IP degree of protection":"IP20 front face conforming to IEC 60529","Pole contact composition":"5 NO","Product or component type":"Control relay","[Ue] rated operational voltage":"10 MOhm","Ambient air temperature for storage":"-60...80 °C","Ambient air temperature for operation":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8f4e3f70c86c313a10a425996710e077.pdf","sourceUrl":"https://www.se.com/uk/en/product/CAD506FDS207/tesys-d-control-relay-5-no-690-v-110-v-dc-standard-coil/"},"ai":{"faq":[{"question":"What compliance documentation is available for this relay?","answer":"The relay is certified to EN/IEC 60947-4-1 and 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN 45545: R22 HL3 for railway fire safety. It also meets V0 flame retardance per UL 94 and 850 °C glow-wire per IEC 60695-2-1."},{"question":"What are the key ratings for CAD506FDS207?","answer":"It is a 5 NO control relay with a 110 V DC coil, rated operational voltage of 690 V, and utilisation categories AC-15, DC-13, and AC-14. Operating temperature range is -40 to 70 °C, with IP20 front-face protection."},{"question":"Can this relay be used in railway applications?","answer":"Yes, it is certified to EN 45545: R22 HL3, which covers fire safety requirements for railway rolling stock. This makes it suitable for control circuits in trains and rail infrastructure."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CAD506FDS207","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CAD506FDS207 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}