{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CR1F1504E7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CR1F1504E7","canonicalUrl":"https://aoctrl.com/schneider/CR1F1504E7","factsUrl":"https://aoctrl.com/api/mcp/products/CR1F1504E7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F CR1F1504E7, magnetic contactor, 4P, AC-1 150A at 440V, coil 48 V AC/DC, 250 A Ith.","salesMarkdown":"The coil is bistable: it latches and unlatches with a pulse, not continuous power. Latching takes 35–40 ms, unlatching 50–100 ms. Average consumption peaks at 1100 VA AC 50/60 Hz during latching, then drops to 7.3 VA AC 50/60 Hz unlatching — so the control transformer only needs to supply the pulse, not hold-in current. The control voltage limits are 0.85 to 1.1 Uc for both latching and unlatching, which means the coil will reliably operate with a 48 V supply between about 41 V and 53 V. This contactor is panel-mounted, sized at 301 mm high, 201.5 mm wide, and 171 mm deep — a substantial footprint that needs generous enclosure space and clearance for the arc chutes. The 4-pole configuration with all NO contacts suits it for switching three-phase power plus a neutral, or two independent resistive loads. The rated breaking capacity varies by voltage: 1500 A at 220–440 V, 1200 A at 500 V, 1100 A at 600–690 V, and 450 A at 1000 V — so the interrupting capability drops as voltage rises, which is typical for air-break contactors. The associated fuse ratings are 160 A aM (motor protection) or 250 A gG/BS88 (general purpose) for the power circuit — these are the maximum fuse sizes that coordinate with the contactor's short-circuit withstand. The mechanical durability is 1,000,000 cycles, and the maximum operating rate is 120 cycles per minute at 40 °C, so it can handle frequent switching in resistance welding or furnace control applications.","metaTitle":"Schneider CR1F1504E7 TeSys F Magnetic Contactor, 4P, 150A AC","metaDescription":"Schneider CR1F1504E7 TeSys F magnetic contactor. 4P, 150A AC-1 rated operational current, 48V AC/DC coil. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"171 mm","Range":"TeSys","Width":"201.5 mm","title":"CR1F1504E7","Height":"301 mm","Coil type":"Standard","description":"contacteur bistable CR1F 4P AC1 440V 250 A bobine 48 V","Product name":"TeSys F","Operating time":"35...40 ms latching 50...100 ms unlatching","lifecycle_stage":"current","Average impedance":"0.45 Ohm - Ith 250 A 50 Hz for control circuit","Device short name":"CR1F","Poles description":"4P","Operating altitude":"3000 m without derating","Operating position":"+/- 5°","Average Consumption":"1100 VA AC 50/60 Hz latching 10 VA AC 400 Hz unlatching 1260 VA AC 400 Hz latching 7.3 VA AC 50/60 Hz unlatching 10 VA DC unlatching 1260 VA DC latching","Protective treatment":"TH","Utilisation category":"AC-1","Mechanical durability":"1000000 cycles","Associated fuse rating":"160 A aM for power circuit 250 A BS88 for power circuit 250 A gG for power circuit","Maximum operating rate":"120 cyc/mn 40 °C","Rated breaking capacity":"1100 A at 600...690 V for power circuit 1200 A at 500 V for power circuit 1500 A at 220...440 V for power circuit 450 A at 1000 V for power circuit","Product or component type":"Magnetic contactor","Irms rated making capacity":"1700 A for power circuit","Power dissipation per pole":"18 W AC-1","[Uc] control circuit voltage":"48 V AC 400 Hz 48 V AC 50/60 Hz 48 V DC","[Ui] rated insulation voltage":"Control circuit: 1000 V conforming to BS 775 Control circuit: 1000 V conforming to IEC 60158-1 Control circuit: 1000 V conforming to IEC 60947-4 Control circuit: 1500 V conforming to VDE 0110 group C","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"150 A (at <40 °C) AC/DC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: 1000 V AC Power circuit: 1000 V DC","Ambient air temperature for operation":"-15...70 °C","[Ith] conventional free air thermal current":"250 A (at 40 °C) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d4ca9a6c577206d878946c071ea8ec5d.pdf","sourceUrl":"https://www.se.com/uk/en/product/CR1F1504E7/contacteur-bistable-cr1f-4p-ac1-440v-250-a-bobine-48-v/"},"ai":{"faq":[{"question":"What are the key ratings for the CR1F1504E7?","answer":"The key ratings are: 150 A rated operational current (Ie) in AC-1 at <40 °C, 250 A conventional free-air thermal current (Ith), 48 V AC/DC control voltage, 4-pole NO configuration, and a rated breaking capacity of 1500 A at 220–440 V."},{"question":"What is the CR1F1504E7's depth?","answer":"The depth is 171 mm."},{"question":"What series does the CR1F1504E7 belong to?","answer":"It belongs to the Schneider Electric TeSys F range of magnetic contactors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CR1F1504E7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CR1F1504E7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}