{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CR1F150R7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CR1F150R7","canonicalUrl":"https://aoctrl.com/schneider/CR1F150R7","factsUrl":"https://aoctrl.com/api/mcp/products/CR1F150R7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F magnetic latching contactor, CR1F150R7, 3-pole, 150 A rated operational current (AC-3), 1000 V AC, control circuit 440 V AC 50/60 Hz.","salesMarkdown":"It is rated for motor control (AC-3, AC-4) and resistive loads (AC-1), with a rated operational current of 150 A at AC-3 duty and a maximum operational voltage of 1000 V AC. The AC-3 rating of 150 A is the motor-switching current — the value that governs whether this contactor handles a given three-phase induction motor under starting and running conditions. At 690 V AC, it drives up to 100 kW; at 400 V, 75 kW; at 230 V, 40 kW. Breaking capacity is 1500 A at 220–440 V for the power circuit, dropping to 450 A at 1000 V — this is the fault-clearing ability without welding the contacts, important for coordination with upstream protection. The making capacity is 1700 A, confirming the contactor can close onto a starting motor inrush without contact damage. The latching coil draws 1260 VA on pickup (both AC and DC) but only 10 VA to unlatch — the holding current is zero once latched, which is the defining advantage of a magnetic-latching design. Control voltage is 440 V AC 50/60 Hz, with an operating range of 0.85 to 1.1 times that voltage for both latching and unlatching. Terminals accept lugs, ring terminals, bars up to 120 mm², or two 25 x 3 mm bars; tightening torque is 18 N·m. Operating temperature range is -15 to 70 °C, storage -60 to 80 °C. The TH protective treatment indicates tropicalisation for humid environments. Altitude derating starts above 3000 m.","metaTitle":"Schneider TeSys CR1F150R7 Magnetic Latching Contactor, 150 A","metaDescription":"Schneider Electric TeSys F CR1F150R7 magnetic latching contactor, 3-pole, rated 150 A at AC-3 duty, 1000 V AC. Motor power up to 100 kW at 690 V. Current lifecycle stage. Sourced t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"6.7 in (171 mm)","Range":"TeSys","Width":"6.4 in (163.5 mm)","Height":"6.7 in (170 mm)","Category":"22336-CTR,F-LINE,AC,OPEN,NONREV","Standards":"VDE 0660 NF C 63-110 JEM 1038 IEC 60947-4 BS 5424","Product name":"TeSys F","Motor power kW":"65 kW at 1000 V AC 50/60 Hz 100 kW at 690 V AC 50/60 Hz 90 kW at 500...660 V AC 50/60 Hz 80 kW at 440 V AC 50/60 Hz 80 kW at 415 V AC 50/60 Hz 75 kW at 380...400 V AC 50/60 Hz 40 kW at 220...230 V AC 50/60 Hz","Operating time":"35...40 ms latching 50...100 ms unlatching","lifecycle_stage":"current","Mounting Support":"Notched AM1-EC rail Panel mounting","Average impedance":"0.45 mOhm - Ith 250 A 50 Hz","Device short name":"CR1F","Poles description":"3P","Tightening torque":"159.3 lbf.in (18 N.m)","Device Application":"Control","Operating altitude":"9842.52 ft (3000 m) without derating","Average Consumption":"1260 VA AC 50...400 Hz latching 10 VA AC 50...400 Hz unlatching 1260 VA DC latching 10 VA DC unlatching","Protective treatment":"TH","Utilisation category":"AC-3 AC-1 AC-4","Contactor application":"Motor control Resistive load","Mechanical durability":"1 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"160 A aM at 250 A BS88 at 250 A gG at <= 440 V for power circuit","Maximum operating rate":"120 cyc/h 131 °F (55 °C)","Connections - terminals":"lugs-ring terminals 1 0.2 in² (120 mm²) connector 1 0.2 in² (120 mm²) bars 2 25 x 3 mm","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"1500 A at 220...440 V for power circuit 1200 A at 500 V for power circuit 450 A at 1000 V for power circuit 1100 A at 660/690 V for power circuit","Product or Component Type":"Magnetic latching contactor","motor power HP (UL / CSA)":"125 hp at 575...600 V AC 50/60 Hz for 3 phase motors 100 hp at 460...480 V AC 50/60 Hz for 3 phase motors 50 hp at 220...240 V AC 50/60 Hz for 3 phase motors 40 hp at 200...208 V AC 50/60 Hz for 3 phase motors","Irms rated making capacity":"1700 A for power circuit","Power dissipation per pole":"6 W AC-3 18 W AC-1","[Uc] control circuit voltage":"440 V AC 50/60 Hz","[Ui] rated insulation voltage":"1000 V IEC 60158-1 1000 V IEC 60947-4 1000 V BS 775 1500 V VDE 0110 group C","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"150 A (at 250 A (at 138 A (at <104 °F (40 °C)) at <= 440 V AC AC-4","[Ue] rated operational voltage":"1000 V AC 25...200 Hz","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"5...158 °F (-15...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"1200 A 104 °F (40 °C) - 1 s 1200 A 104 °F (40 °C) - 5 s 1200 A 104 °F (40 °C) - 10 s 700 A 104 °F (40 °C) - 30 s 600 A 104 °F (40 °C) - 1 min 450 A 104 °F (40 °C) - 3 min 350 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"250 A (at 104 °F (40 °C)) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/17e47f863c5990a6009e5de4227cfc25.pdf","sourceUrl":"https://www.se.com/th/en/product/CR1F150R7/bistable-contactor-cr1f-3p-ac1-440v-150-a-coil-440-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/CR1F150R7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for CR1F150R7?","answer":"Rated operational current 150 A at AC-3 duty, maximum operational voltage 1000 V AC, control circuit voltage 440 V AC 50/60 Hz. Motor power ranges from 40 kW at 230 V to 100 kW at 690 V."},{"question":"What standards does CR1F150R7 comply with?","answer":"It complies with IEC 60947-4, VDE 0660, NF C 63-110, JEM 1038, and BS 5424. Rated insulation voltage is 1000 V per IEC 60947-4 and BS 775, and 1500 V per VDE 0110 group C."},{"question":"What is the depth of CR1F150R7?","answer":"Depth is 6.7 inches (171 mm). Width is 6.4 inches (163.5 mm), height is 6.7 inches (170 mm)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CR1F150R7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CR1F150R7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}