{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CR1F265MZ7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CR1F265MZ7","canonicalUrl":"https://aoctrl.com/schneider/CR1F265MZ7","factsUrl":"https://aoctrl.com/api/mcp/products/CR1F265MZ7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F CR1F265MZ7, magnetic latching contactor, 3-pole, 265 A AC-4 at 440 V, 220 V DC coil, 1000 V insulation rating.","salesMarkdown":"The magnetic latching mechanism holds the main poles closed without continuous coil power; it uses a 220 V DC control circuit, drawing 500 W to latch and 40 W to unlatch, with operating times of 45 to 50 ms for latching and 50 to 100 ms for unlatching. Rated insulation voltage is 1000 V per IEC 60947-4, with an impulse withstand voltage of 8 kV, so it's specified for 690 V line-to-line systems with adequate clearance. The conventional free air thermal current (Ith) is 350 A at 40 °C, which sets the continuous current-carrying capacity in an open panel — the AC-4 rating is the limiting factor for motor duty. ## Motor power and application fit Motor power ratings span 75 kW at 220–230 V up to 160 kW at 690 V AC, and 147 kW at 1000 V. For UL/CSA installations, it covers 60 hp at 200–208 V through 175 hp at 575–600 V. This is a large-frame contactor — the 8.4-inch depth and 7.9-inch width reflect the terminal hardware needed for cable lugs up to 240 mm² or bus bars. Tightening torque on the main connections is 35 N·m. Utilisation categories AC-1, AC-3, and AC-4 are all covered. AC-1 (resistive load) power dissipation is 39 W per pole; AC-3 (motor starting) drops to 22 W per pole. The rated breaking capacity at 220–440 V is 2450 A, and the rated short-time withstand current (Icw) is 2200 A for 1 second at 40 °C — enough to coordinate with upstream 315 A aM fuses or 400 A gG fuses. The contactor is designed for panel mounting with lug or bar connections. Protective treatment is TH (tropicalized/humid environment). Maximum operating rate is 120 cycles per hour at 40 °C. No derating required up to 3000 m altitude.","metaTitle":"Schneider CR1F265MZ7 TeSys F Magnetic Latching Contactor, 26","metaDescription":"CR1F265MZ7 is a current-production TeSys F magnetic latching contactor. Rated 265 A AC-4 at 440 V, 3-pole, 220 V DC coil. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"8.4 in (213 mm)","Range":"TeSys","Width":"7.9 in (201.5 mm)","title":"CR1F265MZ7","Height":"8.0 in (203 mm)","Category":"22336-CTR,F-LINE,AC,OPEN,NONREV","description":"TeSys F magnetic latching contactor - 3P - 265 A - 220 V DC coil - low consum.","Product name":"TeSys F","Motor power kW":"147 kW at 1000 V AC 50/60 Hz 160 kW at 690 V AC 50/60 Hz 160 kW at 500...660 V AC 50/60 Hz 140 kW at 440 V AC 50/60 Hz 140 kW at 415 V AC 50/60 Hz 132 kW at 380...400 V AC 50/60 Hz 75 kW at 220...230 V AC 50/60 Hz","Operating time":"50...100 ms unlatching 45...50 ms latching","lifecycle_stage":"current","Average impedance":"0.32 mOhm - Ith 350 A 50 Hz","Device short name":"CR1F","Poles description":"3P","Tightening torque":"309.8 lbf.in (35 N.m)","Device Application":"Control","Operating altitude":"9842.52 ft (3000 m) without derating","Average Consumption":"500 W DC latching 40 W DC unlatching","Protective treatment":"TH","Utilisation category":"AC-4 AC-3 AC-1","Contactor application":"Motor control Resistive load","Mechanical durability":"1 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"315 A aM at 400 A BS88 at 400 A gG at <= 440 V","Maximum operating rate":"120 cyc/h 104 °F (40 °C)","Connections - terminals":"lugs-ring terminals 1 0.4 in² (240 mm²) connector 1 0.4 in² (240 mm²) bars 2 32 x 4 mm","Rated breaking capacity":"2450 A at 220...440 V 2200 A at 500 V 800 A at 1000 V 1700 A at 660/690 V","Product or Component Type":"Magnetic latching contactor","motor power HP (UL / CSA)":"175 hp at 575...600 V AC 50/60 Hz for 3 phase motors 150 hp at 460...480 V AC 50/60 Hz for 3 phase motors 75 hp at 220...240 V AC 50/60 Hz for 3 phase motors 60 hp at 200...208 V AC 50/60 Hz for 3 phase motors","Irms rated making capacity":"2940 A","Power dissipation per pole":"22 W AC-3 39 W AC-1","[Uc] control circuit voltage":"220 V DC low consumption","[Ui] rated insulation voltage":"1000 V IEC 60158-1 1000 V IEC 60947-4 1000 V BS 775 1500 V VDE 0110 group C","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"265 A (at 350 A (at 245 A (at <104 °F (40 °C)) at <= 440 V AC AC-4","[Ue] rated operational voltage":"1000 V AC 25...200 Hz","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"5...158 °F (-15...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"2200 A 104 °F (40 °C) - 1 s 2200 A 104 °F (40 °C) - 5 s 2200 A 104 °F (40 °C) - 10 s 1230 A 104 °F (40 °C) - 30 s 950 A 104 °F (40 °C) - 1 min 620 A 104 °F (40 °C) - 3 min 480 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"350 A (at 104 °F (40 °C))"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5fdc74e00c0c5250a181dfe0ff309097.pdf","sourceUrl":"https://www.se.com/sg/en/product/CR1F265MZ7/tesys-f-magnetic-latching-contactor-3p-265-a-220-v-dc-coil-low-consum-/"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"Rated operational current (Ie) is 265 A in AC-4 duty at ≤440 V, with a conventional free air thermal current (Ith) of 350 A at 40 °C. Rated operational voltage is 1000 V AC, with an insulation voltage of 1000 V per IEC 60947-4. The control circuit is 220 V DC. Motor power ranges from 75 kW at 230 V to 160 kW at 690 V."},{"question":"What fuse coordination is recommended?","answer":"Associated fuse ratings are 315 A aM, 400 A BS88, or 400 A gG at ≤440 V. The short-time withstand current (Icw) of 2200 A for 1 second supports this coordination."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CR1F265MZ7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CR1F265MZ7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}