{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CR1F4004E7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CR1F4004E7","canonicalUrl":"https://aoctrl.com/schneider/CR1F4004E7","factsUrl":"https://aoctrl.com/api/mcp/products/CR1F4004E7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F CR1F4004E7, 4-pole magnetic latching contactor, 400 A rated operational current (AC-4), 48 V AC/DC control voltage, IP20 front face.","salesMarkdown":"It carries a rated operational current of 400 A in AC-4 duty (the category for inching and plugging of motors), with a rated operational voltage up to 1000 V AC. The magnetic latching mechanism holds the main contacts closed without continuous coil power — a 48 V AC/DC pulse latches it, a separate pulse unlatches it — which means the contactor stays in its last commanded state through a power loss, useful for fail-safe or energy-conscious applications. The 4 NO (normally open) power poles handle the main load; the front face is IP20 protected against finger contact, so it's safe in an open panel. This contactor is sized for substantial three-phase induction motors. At 380–400 V AC, it switches a 200 kW motor; at 440 V, 250 kW; at 690 V, 280 kW. For UL/CSA installations, the horsepower ratings are 250 hp at 460–480 V and 300 hp at 575–600 V. These figures are for AC-3 duty (starting and stopping a running motor) at 50/60 Hz. The rated breaking capacity tells you what fault it can safely interrupt: 4000 A at 220–440 V, 3000 A at 660/690 V, and 1200 A at 1000 V — enough to clear a bolted fault on a large motor branch circuit. The associated fuse recommendation (400 A aM or gG up to 500 A BS88) gives the upstream protection boundary for the power circuit. ## Coil control and power consumption The latching coil draws 1600 VA during the latching pulse (AC 50–400 Hz or DC) and only 16 VA during the unlatching pulse. That's a brief, high-inrush pull-in, then zero holding power once latched — the contactor stays closed on the magnetic latch alone. The control voltage limits are 0.85 to 1.1 times the nominal 48 V UC for both latching and unlatching, so your control supply needs to stay within that band. Operating time is 40–75 ms to latch, 50–100 ms to unlatch, which is typical for a contactor this size. ## Mounting, connections, and environmental limits Mounts on a notched AM1-EC rail — a standard DIN-style rail for large contactors. The main power connections accept lugs or ring terminals up to 150 mm² (0.2 in²) or bars 30 x 5 mm, with a tightening torque of 35 N.m (309.8 lbf.in). The contactor measures 261 mm wide, 206 mm high, and 219 mm deep — a substantial footprint, so check your panel depth before committing. Maximum operating rate is 120 cycles per hour at 40 °C, and the mechanical durability is rated at 1 million cycles. Power dissipation per pole is 45 W in AC-3 and 70 W in AC-1, which adds up to 180–280 W total heat to evacuate from the enclosure.","metaTitle":"CR1F4004E7 TeSys F Magnetic Latching Contactor, 4P, 400 A AC","metaDescription":"CR1F4004E7 TeSys F magnetic latching contactor, 4 NO poles, 400 A AC-4 rated operational current, 48 V AC/DC coil. Active production. Sourced to order. Standards: VDE 0660, IEC 609","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"8.6 in (219 mm)","Range":"TeSys","Width":"10.3 in (261 mm)","title":"CR1F4004E7","Height":"8.1 in (206 mm)","Category":"22336-CTR,F-LINE,AC,OPEN,NONREV","Standards":"VDE 0660 IEC 60947-4 JEM 1038 NF C 63-110 BS 5424","description":"Bistable contactor CR1-F - 4P - AC-1 440V 500 A - coil 48 V","Product name":"TeSys F","Motor power kW":"185 kW at 1000 V AC 50/60 Hz 280 kW at 690 V AC 50/60 Hz 257 kW at 500...660 V AC 50/60 Hz 250 kW at 440 V AC 50/60 Hz 220 kW at 415 V AC 50/60 Hz 200 kW at 380...400 V AC 50/60 Hz 110 kW at 220...230 V AC 50/60 Hz","Operating time":"40...75 ms latching 50...100 ms unlatching","lifecycle_stage":"current","Mounting Support":"Notched AM1-EC rail","Average impedance":"0.28 mOhm - Ith 500 A 50 Hz","Device short name":"CR1F","Poles description":"4P","Tightening torque":"309.8 lbf.in (35 N.m)","Device Application":"Control","Operating altitude":"9842.52 ft (3000 m) without derating","Average Consumption":"1600 VA AC 50...400 Hz latching 16 VA AC 50...400 Hz unlatching 1600 VA DC latching 16 VA DC unlatching","Protective treatment":"TH","Utilisation category":"AC-4 AC-1 AC-3","Contactor application":"Resistive load Motor control","Mechanical durability":"1 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"400 A aM at 500 A BS88 at 500 A gG at <= 440 V for power circuit","Maximum operating rate":"120 cyc/h 104 °F (40 °C)","Connections - terminals":"lugs-ring terminals 2 0.2 in² (150 mm²) bars 2 30 x 5 mm","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"4000 A at 220...440 V for power circuit 3500 A at 500 V for power circuit 1200 A at 1000 V for power circuit 3000 A at 660/690 V for power circuit","Product or Component Type":"Magnetic latching contactor","motor power HP (UL / CSA)":"300 hp at 575...600 V AC 50/60 Hz for 3 phase motors 250 hp at 460...480 V AC 50/60 Hz for 3 phase motors 125 hp at 220...240 V AC 50/60 Hz for 3 phase motors 100 hp at 200...208 V AC 50/60 Hz for 3 phase motors","Irms rated making capacity":"4500 A for power circuit","Power dissipation per pole":"45 W AC-3 70 W AC-1","[Uc] control circuit voltage":"48 V AC 50...400 Hz 48 V DC standard","[Ui] rated insulation voltage":"1000 V IEC 60158-1 1000 V IEC 60947-4 1000 V BS 775 1500 V VDE 0110 group C","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"400 A (at 500 A (at 370 A (at <104 °F (40 °C)) at <= 440 V AC AC-4","[Ue] rated operational voltage":"1000 V AC 25...200 Hz","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"5...158 °F (-15...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3600 A 104 °F (40 °C) - 1 s 3600 A 104 °F (40 °C) - 5 s 3600 A 104 °F (40 °C) - 10 s 2400 A 104 °F (40 °C) - 30 s 1700 A 104 °F (40 °C) - 1 min 1200 A 104 °F (40 °C) - 3 min 1000 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"500 A (at 104 °F (40 °C)) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/572231875da83da64d2c6efa8e4509a7.pdf","sourceUrl":"https://www.se.com/th/en/product/CR1F4004E7/bistable-contactor-cr1f-4p-ac1-440v-500-a-coil-48-v/"},"ai":{"faq":[{"question":"What is the CR1F4004E7's depth?","answer":"The depth is 8.6 inches (219 mm)."},{"question":"What is the CR1F4004E7's control voltage?","answer":"The control circuit voltage is 48 V AC (50–400 Hz) or 48 V DC standard. The latching and unlatching voltage limits are 0.85 to 1.1 times the nominal Uc."},{"question":"What standards does the CR1F4004E7 comply with?","answer":"It complies with VDE 0660, IEC 60947-4, JEM 1038, NF C 63-110, and BS 5424. It also carries UL/CSA horsepower ratings for North American installations."},{"question":"What is the rated breaking capacity of the CR1F4004E7?","answer":"For the power circuit: 4000 A at 220–440 V, 3500 A at 500 V, 3000 A at 660/690 V, and 1200 A at 1000 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CR1F4004E7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CR1F4004E7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}