{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CR1F4004U7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CR1F4004U7","canonicalUrl":"https://aoctrl.com/schneider/CR1F4004U7","factsUrl":"https://aoctrl.com/api/mcp/products/CR1F4004U7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F CR1F4004U7, magnetic latching contactor, 4-pole, 400 A rated operational current (AC-3), 240 V AC 50/60 Hz coil.","salesMarkdown":"The Schneider Electric CR1F4004U7 is a TeSys F magnetic latching contactor, a 4-pole device (4 NO) rated for 400 A at <= 440 V AC in AC-3 duty, per IEC 60947-4. The 240 V AC 50/60 Hz control circuit draws 1600 VA during latching and 16 VA during unlatching; the coil holds between 0.85 and 1.1 Uc. The 400 A AC-3 rating governs motor switching up to that current — the contactor is sized for a 200 kW motor at 380...400 V AC or 250 hp at 460...480 V AC (UL/CSA). AC-1 resistive load rating is higher; AC-4 (inching/plugging) duty is also listed, but the AC-3 figure is the one that decides the BOM line for standard motor starts. Power dissipation per pole is 45 W in AC-3 and 70 W in AC-1 — relevant for thermal management inside a panel. The associated fuse rating is 400 A aM or 500 A gG at <= 440 V for the power circuit. Mounts on a notched AM1-EC rail. Panel cutout dimensions: 8.6 in (219 mm) depth, 10.3 in (261 mm) width, 8.1 in (206 mm) height. Terminals accept lugs or ring terminals up to 150 mm², or bars 30 x 5 mm; tightening torque is 309.8 lbf.in (35 N.m). IP20 front face per IEC 60529 — suitable for enclosed panel use, not washdown. Compliant with BS 5424, VDE 0660, NF C 63-110, JEM 1038, and IEC 60947-4. Rated insulation voltage is 1000 V per IEC 60947-4 and BS 775. Operating temperature range is 5...158 °F (-15...70 °C); storage range is -76...176 °F (-60...80 °C). Altitude rating is 9842.52 ft (3000 m) without derating. Protective treatment is TH (tropicalized).","metaTitle":"TeSys F CR1F4004U7 Magnetic Latching Contactor, 400 A AC-3,","metaDescription":"Schneider Electric TeSys F CR1F4004U7 magnetic latching contactor. 400 A rated operational current (AC-3), 4 NO poles, 240 V AC coil. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"8.6 in (219 mm)","Range":"TeSys","Width":"10.3 in (261 mm)","title":"CR1F4004U7","Height":"8.1 in (206 mm)","Category":"22336-CTR,F-LINE,AC,OPEN,NONREV","Standards":"BS 5424 VDE 0660 NF C 63-110 JEM 1038 IEC 60947-4","description":"Bistable contactor CR1-F - 4P - AC-1 440V 500 A - coil 240 V","Product name":"TeSys F","Motor power kW":"185 kW at 1000 V AC 50/60 Hz 280 kW at 690 V AC 50/60 Hz 257 kW at 500...660 V AC 50/60 Hz 250 kW at 440 V AC 50/60 Hz 220 kW at 415 V AC 50/60 Hz 200 kW at 380...400 V AC 50/60 Hz 110 kW at 220...230 V AC 50/60 Hz","Operating time":"40...75 ms latching 50...100 ms unlatching","lifecycle_stage":"current","Mounting Support":"Notched AM1-EC rail","Average impedance":"0.28 mOhm - Ith 500 A 50 Hz","Device short name":"CR1F","Poles description":"4P","Tightening torque":"309.8 lbf.in (35 N.m)","Device Application":"Control","Operating altitude":"9842.52 ft (3000 m) without derating","Average Consumption":"1600 VA AC 50...400 Hz latching 16 VA AC 50...400 Hz unlatching 1600 VA DC latching 16 VA DC unlatching","Protective treatment":"TH","Utilisation category":"AC-4 AC-1 AC-3","Contactor application":"Resistive load Motor control","Mechanical durability":"1 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"400 A aM at 500 A BS88 at 500 A gG at <= 440 V for power circuit","Maximum operating rate":"120 cyc/h 104 °F (40 °C)","Connections - terminals":"lugs-ring terminals 2 0.2 in² (150 mm²) bars 2 30 x 5 mm","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"4000 A at 220...440 V for power circuit 3500 A at 500 V for power circuit 1200 A at 1000 V for power circuit 3000 A at 660/690 V for power circuit","Product or Component Type":"Magnetic latching contactor","motor power HP (UL / CSA)":"300 hp at 575...600 V AC 50/60 Hz for 3 phase motors 250 hp at 460...480 V AC 50/60 Hz for 3 phase motors 125 hp at 220...240 V AC 50/60 Hz for 3 phase motors 100 hp at 200...208 V AC 50/60 Hz for 3 phase motors","Irms rated making capacity":"4500 A for power circuit","Power dissipation per pole":"45 W AC-3 70 W AC-1","[Uc] control circuit voltage":"240 V AC 50/60 Hz","[Ui] rated insulation voltage":"1000 V IEC 60158-1 1000 V IEC 60947-4 1000 V BS 775 1500 V VDE 0110 group C","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"400 A (at 500 A (at 370 A (at <104 °F (40 °C)) at <= 440 V AC AC-4","[Ue] rated operational voltage":"1000 V AC 25...200 Hz","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"5...158 °F (-15...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"3600 A 104 °F (40 °C) - 1 s 3600 A 104 °F (40 °C) - 5 s 3600 A 104 °F (40 °C) - 10 s 2400 A 104 °F (40 °C) - 30 s 1700 A 104 °F (40 °C) - 1 min 1200 A 104 °F (40 °C) - 3 min 1000 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"500 A (at 104 °F (40 °C)) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c99d898a7dad0d38f0f781505f1c4619.pdf","sourceUrl":"https://www.se.com/sg/en/product/CR1F4004U7/bistable-contactor-cr1f-4p-ac1-440v-500-a-coil-240-v/"},"ai":{"faq":[{"question":"What are the key ratings for the CR1F4004U7?","answer":"Rated operational current is 400 A in AC-3 at <= 440 V AC. Rated operational voltage is 1000 V AC. Control circuit voltage is 240 V AC 50/60 Hz. Breaking capacity is 4000 A at 220...440 V for the power circuit."},{"question":"What compliance standards does the CR1F4004U7 meet?","answer":"It complies with BS 5424, VDE 0660, NF C 63-110, JEM 1038, and IEC 60947-4. Rated insulation voltage is 1000 V per IEC 60947-4 and BS 775."},{"question":"What are the physical dimensions of the CR1F4004U7?","answer":"Depth is 8.6 in (219 mm), width is 10.3 in (261 mm), height is 8.1 in (206 mm)."},{"question":"What is the closest alternative to the CR1F4004U7 within the TeSys F family?","answer":"Within the TeSys F family, the closest peer would be a contactor with the same pole count and similar current rating but a different coil voltage — the CR1F4004U7 is specific to 240 V AC control. No pin-compatible drop-in replacement with a different coil voltage is listed as a direct successor; verify coil compatibility before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CR1F4004U7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CR1F4004U7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}