{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CR1F6304N7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CR1F6304N7","canonicalUrl":"https://aoctrl.com/schneider/CR1F6304N7","factsUrl":"https://aoctrl.com/api/mcp/products/CR1F6304N7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F CR1F6304N7 magnetic latching contactor, 4-pole, 630 A rated operational current, 1000 V AC, IP20 front face.","salesMarkdown":"The Schneider Electric TeSys F CR1F6304N7 is a 4-pole magnetic latching contactor rated for 630 A operational current at up to 1000 V AC. The latching mechanism holds the main poles in position without continuous coil power; unlatching requires a separate pulse. That 630 A figure is the rated operational current (Ie) in AC-3 duty for motor switching; the same contactor carries 1000 A in AC-1 resistive load service, so the actual current you can switch depends on the load type. Motor power capability spans from 200 kW at 220–230 V AC up to 450 kW at 690 V and 1000 V AC (50/60 Hz). Under UL/CSA ratings, it handles 800 hp at 575–600 V for three-phase motors. That's a big contactor — sized for large pumps, compressors, conveyors, or any motor load where you need a single switching device rather than paralleling smaller units. For resistive loads (AC-1), the same contactor is good for 1000 A, which is the thermal current (Ith) rating. The utilisation categories AC-1, AC-3, and AC-4 cover the full range from resistive heating banks through standard squirrel-cage motor starting to plugging and inching duty. Breaking capacity is substantial: 6300 A at 220–440 V, tapering to 3200 A at 1000 V for the power circuit. That's the fault-clearing capability the contactor can handle without welding its contacts — relevant for coordination studies where the contactor sits downstream of a fuse or breaker. The associated fuse recommendation is 630 A aM or gG type, which sets the short-circuit protection boundary. Control circuit voltage is 415 V AC 50/60 Hz, with latching and unlatching both requiring 0.85 to 1.1 times Uc. The coil draw spikes at 2300 VA during the latching pulse, then drops to 11 VA for the unlatching pulse — that's a momentary surge, not continuous. The operating time is 40–80 ms to latch and 50–100 ms to unlatch, which matters if you're sequencing contactors in a transfer scheme. This contactor mounts on a notched AM1-EC rail — that's a heavy-duty mounting channel, not a standard DIN rail. The dimensions are substantial: 389 mm wide, 304 mm high, 255 mm deep. Panel layout needs to account for the bar-type terminals (2 bars 60 x 5 mm) and the tightening torque of 58 N.m on the power connections. The TH protective treatment indicates it's tropicalised for humidity resistance. Maximum operating rate is 120 cycles per hour at 40 °C, and mechanical durability is rated at 1 million cycles — so it's built for a long service life in continuous-duty applications.","metaTitle":"Schneider TeSys CR1F6304N7 Magnetic Latching Contactor, 630","metaDescription":"Schneider Electric TeSys F CR1F6304N7 magnetic latching contactor, 4-pole, 630 A rated operational current at 1000 V AC. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"10.04 in (255 mm)","Range":"TeSys","Width":"15.3 in (389 mm)","Height":"12.0 in (304 mm)","Category":"22331-CTR,F-LINE,DC,OPEN,NONREV","Standards":"VDE 0660 BS 5424 IEC 60947-4 JEM 1038 NF C 63-110","Product name":"TeSys F","Motor power kW":"450 kW at 1000 V AC 50/60 Hz 450 kW at 690 V AC 50/60 Hz 400 kW at 500...660 V AC 50/60 Hz 400 kW at 440 V AC 50/60 Hz 375 kW at 415 V AC 50/60 Hz 335 kW at 380...400 V AC 50/60 Hz 200 kW at 220...230 V AC 50/60 Hz","Operating time":"40...80 ms latching 50...100 ms unlatching","lifecycle_stage":"current","Mounting Support":"Notched AM1-EC rail","Average impedance":"0.12 mOhm - Ith 1000 A 50 Hz","Device short name":"CR1F","Poles description":"4P","Tightening torque":"513.3 lbf.in (58 N.m)","Device Application":"Control","Operating altitude":"9842.52 ft (3000 m) without derating","Average Consumption":"11 VA AC 50...400 Hz unlatching 2300 VA AC 50...400 Hz latching 11 VA DC unlatching 2300 VA DC latching","Protective treatment":"TH","Utilisation category":"AC-1 AC-3 AC-4","Contactor application":"Motor control Resistive load","Mechanical durability":"1 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"630 A aM at 1000 A BS88 at 1000 A gG at <= 440 V for power circuit","Maximum operating rate":"120 cyc/h 104 °F (40 °C)","Connections - terminals":"bars 2 60 x 5 mm","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"3200 A at 1000 V 6300 A at 220...440 V for power circuit 5400 A at 500 V for power circuit 4600 A at 660/690 V for power circuit","Product or Component Type":"Magnetic latching contactor","motor power HP (UL / CSA)":"800 hp at 575...600 V AC 50/60 Hz for 3 phase motors 600 hp at 460...480 V AC 50/60 Hz for 3 phase motors 300 hp at 220...240 V AC 50/60 Hz for 3 phase motors 250 hp at 200...208 V AC 50/60 Hz for 3 phase motors","Irms rated making capacity":"6740 A for power circuit","Power dissipation per pole":"48 W AC-3 120 W AC-1","[Uc] control circuit voltage":"415 V AC 50/60 Hz","[Ui] rated insulation voltage":"1000 V IEC 60158-1 1000 V IEC 60947-4 1000 V BS 775 1500 V VDE 0110 group C","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc","Power Pole Contact Composition":"4 NO","[Ie] rated operational current":"630 A (at 1000 A (at 560 A (at <104 °F (40 °C)) at <= 440 V AC AC-4","[Ue] rated operational voltage":"1000 V AC 25...200 Hz","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"5...158 °F (-15...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"5.05 kA 104 °F (40 °C) - 1 s 5.05 kA 104 °F (40 °C) - 5 s 5.05 kA 104 °F (40 °C) - 10 s 4400 A 104 °F (40 °C) - 30 s 3400 A 104 °F (40 °C) - 1 min 2200 A 104 °F (40 °C) - 3 min 1600 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"1000 A (at 104 °F (40 °C)) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/03993a9a26c12c866936979bfe46ff23.pdf","sourceUrl":"https://www.se.com/vn/en/product/CR1F6304N7/bistable-contactor-cr1f-4p-ac1-440v-1000-a-coil-415-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/CR1F6304N7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The critical ratings are 630 A rated operational current (Ie) in AC-3 motor duty, 1000 V AC rated operational voltage (Ue), 415 V AC control circuit voltage, and 4-pole NO contact configuration. For resistive loads (AC-1), the contactor carries 1000 A."},{"question":"What standards does this contactor comply with?","answer":"It complies with IEC 60947-4, VDE 0660, BS 5424, JEM 1038, and NF C 63-110. The rated insulation voltage (Ui) is 1000 V per IEC 60947-4 and IEC 60158-1, with 1500 V per VDE 0110 group C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CR1F6304N7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CR1F6304N7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}