{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CR1F630N7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CR1F630N7","canonicalUrl":"https://aoctrl.com/schneider/CR1F630N7","factsUrl":"https://aoctrl.com/api/mcp/products/CR1F630N7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys F magnetic latching contactor, CR1F630N7, 3-pole, 630 A rated operational current, 1000 V AC.","salesMarkdown":"The CR1F630N7 is a 3-pole magnetic latching contactor from the Schneider Electric TeSys F range. Rated for AC-1, AC-3, and AC-4 utilisation categories, it handles resistive loads and motor starting/plugging duties. Motor power ratings span 200 kW at 220–230 V up to 450 kW at 1000 V AC (50/60 Hz). UL/CSA motor horsepower ratings are also listed: 800 hp at 575–600 V. The latching mechanism holds the main contacts closed without continuous coil power, which cuts standby losses. Control circuit voltage is 415 V AC 50/60 Hz, with latching and unlatching power consumption spiking to 2300 VA during the switching transient, then dropping to 11 VA for hold. For AC-4 duty (plugging/inching), the rating drops to 560 A at ≤440 V — a real derating that matters if your motor cycle includes frequent reversals. Rated breaking capacity reaches 6300 A at 220–440 V, tapering to 3200 A at 1000 V. This tells you the fault current the contactor can interrupt without welding contacts. Pair it with the associated fuse rating (630 A aM or gG) for coordinated protection. Mechanical durability is rated at 1 million cycles. The maximum operating rate is 120 cycles per hour at 40 °C — fine for most process conveyors and pump starts, but not for high-speed indexing applications. Mounts on a notched AM1-EC rail. Operates without derating up to 3000 m altitude. Above that, expect reduced dielectric strength and cooling — consult the thermal derating curve if your site is above 3000 m. Compliance with VDE 0660, IEC 60947-4, BS 5424, JEM 1038, and NF C 63-110 standards is listed. The rated insulation voltage is 1000 V per IEC 60947-4 and 1500 V per VDE 0110 group C. Protective treatment is TH (tropicalised) for humid environments.","metaTitle":"CR1F630N7 TeSys F Magnetic Latching Contactor, 630 A, 3P","metaDescription":"CR1F630N7 TeSys F magnetic latching contactor, 630 A rated operational current, 3 poles, 1000 V AC. Current lifecycle stage. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"10.04 in (255 mm)","Range":"TeSys","Width":"12.2 in (309 mm)","Height":"12.0 in (304 mm)","Category":"22331-CTR,F-LINE,DC,OPEN,NONREV","Standards":"VDE 0660 IEC 60947-4 BS 5424 JEM 1038 NF C 63-110","Product name":"TeSys F","Motor power kW":"450 kW at 1000 V AC 50/60 Hz 450 kW at 690 V AC 50/60 Hz 400 kW at 500...660 V AC 50/60 Hz 400 kW at 440 V AC 50/60 Hz 375 kW at 415 V AC 50/60 Hz 335 kW at 380...400 V AC 50/60 Hz 200 kW at 220...230 V AC 50/60 Hz","Operating time":"40...80 ms latching 50...100 ms unlatching","lifecycle_stage":"current","Mounting Support":"Notched AM1-EC rail","Average impedance":"0.12 mOhm - Ith 1000 A 50 Hz","Device short name":"CR1F","Poles description":"3P","Tightening torque":"513.3 lbf.in (58 N.m)","Device Application":"Control","Operating altitude":"9842.52 ft (3000 m) without derating","Average Consumption":"11 VA AC 50...400 Hz unlatching 2300 VA AC 50...400 Hz latching 11 VA DC unlatching 2300 VA DC latching","Protective treatment":"TH","Utilisation category":"AC-4 AC-3 AC-1","Contactor application":"Resistive load Motor control","Mechanical durability":"1 Mcycles","Nbr. of units in pkg.":"1","Associated fuse rating":"630 A aM at 1000 A BS88 at 1000 A gG at <= 440 V for power circuit","Maximum operating rate":"120 cyc/h 104 °F (40 °C)","Connections - terminals":"bars 2 60 x 5 mm","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"3200 A at 1000 V 6300 A at 220...440 V for power circuit 5400 A at 500 V for power circuit 4600 A at 660/690 V for power circuit","Product or Component Type":"Magnetic latching contactor","motor power HP (UL / CSA)":"800 hp at 575...600 V AC 50/60 Hz for 3 phase motors 600 hp at 460...480 V AC 50/60 Hz for 3 phase motors 300 hp at 220...240 V AC 50/60 Hz for 3 phase motors 250 hp at 200...208 V AC 50/60 Hz for 3 phase motors","Irms rated making capacity":"6740 A for power circuit","Power dissipation per pole":"48 W AC-3 120 W AC-1","[Uc] control circuit voltage":"415 V AC 50/60 Hz","[Ui] rated insulation voltage":"1000 V IEC 60158-1 1000 V IEC 60947-4 1000 V BS 775 1500 V VDE 0110 group C","Control circuit voltage limits":"Latching: 0.85...1.1 Uc Unlatching: 0.85...1.1 Uc","Power Pole Contact Composition":"3 NO","[Ie] rated operational current":"630 A (at 1000 A (at 560 A (at <104 °F (40 °C)) at <= 440 V AC AC-4","[Ue] rated operational voltage":"1000 V AC 25...200 Hz","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"5...158 °F (-15...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"5.05 kA 104 °F (40 °C) - 1 s 5.05 kA 104 °F (40 °C) - 5 s 5.05 kA 104 °F (40 °C) - 10 s 4400 A 104 °F (40 °C) - 30 s 3400 A 104 °F (40 °C) - 1 min 2200 A 104 °F (40 °C) - 3 min 1600 A 104 °F (40 °C) - 10 min","[Ith] conventional free air thermal current":"1000 A (at 104 °F (40 °C)) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ec6ea93de82f6d435f8ceb06b805a60b.pdf","sourceUrl":"https://www.se.com/vn/en/product/CR1F630N7/bistable-contactor-cr1f-3p-ac3-440v-630-a-coil-415-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/CR1F630N7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the CR1F630N7?","answer":"Rated operational current is 630 A at ≤440 V AC (AC-3), with a maximum operational voltage of 1000 V AC. It is a 3-pole magnetic latching contactor from the TeSys F range, rated for motor power up to 450 kW at 1000 V."},{"question":"What compliance documentation does the CR1F630N7 carry?","answer":"The contactor complies with VDE 0660, IEC 60947-4, BS 5424, JEM 1038, and NF C 63-110. Rated insulation voltage is 1000 V per IEC 60947-4 and 1500 V per VDE 0110 group C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CR1F630N7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CR1F630N7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}