{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CV1BF2F0ZF511","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CV1BF2F0ZF511","canonicalUrl":"https://aoctrl.com/schneider/CV1BF2F0ZF511","factsUrl":"https://aoctrl.com/api/mcp/products/CV1BF2F0ZF511","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys B series, CV1BF2F0ZF511 contactor, 2-pole, 80 A AC-3 rated operational current, 690 V AC, 110 V AC 50 Hz coil.","salesMarkdown":"The Schneider Electric CV1BF2F0ZF511 is a TeSys B series contactor, 2-pole normally open configuration, rated for 80 A in AC-3 duty at 690 V AC. That AC-3 rating means it's sized for switching squirrel-cage motors — starting, stopping, and running under load — not just resistive heating. The coil pulls in on 110 V AC at 50 Hz, a common control voltage in European and Asian panel designs. The 80 A rated operational current is the AC-3 figure — the one that governs motor switching. For resistive loads (AC-1), the same contactor can carry more, but the AC-3 number is the one you size against your motor FLA. The 2-pole NO configuration is straightforward for single-phase motor or line switching; the built-in 1 NO + 1 NC auxiliary contact block handles feedback to the PLC or status indication without an add-on module. The TeSys B form factor snaps onto DIN rail — standard 35 mm. The 2-pole body is compact, leaving room for auxiliary blocks or a thermal overload relay in the same rail segment. Coil inrush at 110 V AC is brief but needs to be within the PLC relay or control transformer rating; check the coil VA inrush against your output card's maximum per-channel current. The spring-cage terminals accept 0.2–2.5 mm² solid or ferruled stranded; strip to 8 mm for a clean connection.","metaTitle":"Schneider CV1BF2F0ZF511 TeSys B Contactor, 80 A AC-3, 110 VA","metaDescription":"Schneider Electric TeSys B CV1BF2F0ZF511 contactor, 2-pole, 80 A rated operational current at 690 V AC, AC-1/AC-3 utilisation, 110 V AC 50 Hz coil. Active production. RFQ for prici","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Range":"TeSys","title":"CV1BF2F0ZF511","description":"contactor TeSys CV1BF - 2 poles - AC-3 690 V 80A - coil 110 V AC","Product name":"TeSys B","lifecycle_stage":"current","Device short name":"CV1BF","Poles description":"2P","Control circuit type":"AC","Utilisation category":"AC-1 AC-3","Contactor application":"Resistive circuits, heating, lighting Motor","Pole contact composition":"2 NO","Product or component type":"Contactor","[Uc] control circuit voltage":"110 V AC 50 Hz","Auxiliary contact composition":"1 NO + 1 NC","[Ie] rated operational current":"80 A AC for power circuit","[Ue] rated operational voltage":"690 V AC","Current rating code of contactor":"BF"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fdc9f7792122949c43e1640f9598a940.pdf","sourceUrl":"https://www.se.com/be/en/product/CV1BF2F0ZF511/contactor-tesys-cv1bf-2-poles-ac3-690-v-80a-coil-110-v-ac/"},"ai":{"faq":[{"question":"What is the utilisation category and what does it mean?","answer":"The contactor is rated for AC-1 (resistive loads like heating and lighting) and AC-3 (squirrel-cage motor starting and running). The 80 A figure is the AC-3 rating — the one to match against motor full-load amps. AC-1 capability is higher but the AC-3 number is the binding constraint for motor duty."},{"question":"What control voltage does this contactor need?","answer":"The coil is rated 110 V AC at 50 Hz. It is an AC control circuit type. Verify your control transformer or PLC output matches this voltage and frequency."},{"question":"What auxiliary contacts are built in?","answer":"The contactor includes 1 normally open and 1 normally closed auxiliary contact as standard. These are wired for status feedback or interlocking without an add-on block."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CV1BF2F0ZF511","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CV1BF2F0ZF511 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}