{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"CV1BG2G0ZMD00","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"CV1BG2G0ZMD00","canonicalUrl":"https://aoctrl.com/schneider/CV1BG2G0ZMD00","factsUrl":"https://aoctrl.com/api/mcp/products/CV1BG2G0ZMD00","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys B standard contactor, 2 poles, 200 A, coil 220 V DC, IP00, IEC 60947-4.","salesMarkdown":"The Schneider Electric CV1BG2G0ZMD00 is a TeSys B standard contactor, 2-pole, rated for 200 A in AC-1 and AC-3 utilisation categories. The 220 V DC coil pulls in at 0.85 to 1.1 Uc and drops out between 0.1 and 0.65 Uc at 55 °C, so it's a straight DC coil — no rectifier needed, but watch the dropout range if your control supply dips. That 200 A figure is the conventional free-air thermal current at 40 °C, which means it'll carry that continuously in open air; derate if you stuff it in a tight panel. This is a two-pole contactor with both poles normally open (2 NO). It's built for switching motor loads (AC-3) and resistive circuits like heating and lighting (AC-1). If you're running a 200 A resistive heater bank, this is a direct fit. For motor duty at 200 A, that's roughly a 90–110 kW motor at 400 V, but confirm the actual motor FLA against the AC-3 rating in your specific voltage. It'll live inside a control cabinet or a machine enclosure. The control circuit terminates with lugs or a connector; power connections are cable with lug. Shock and vibration resistance is 4 gn / 2 gn, which is typical for industrial panel gear — fine for most fixed installations, but if it's going on a vibrating conveyor or mobile equipment, you'll want to check the mounting orientation and add damping. Maximum operating altitude is 2000 m without derating. If you're above that, the air density drop reduces the cooling and dielectric strength — standard IEC derating applies.","metaTitle":"TeSys CV1BG2G0ZMD00 Contactor, 200A, 2 Poles, 220V DC Coil","metaDescription":"Schneider TeSys B contactor CV1BG2G0ZMD00, 2-pole, 200A AC rated, 220V DC coil. Active production. Sourced to order. IEC 60947-4.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Range":"TeSys","title":"CV1BG2G0ZMD00","Category":"18402-WORLD SERVICE PARTS(CONTROL ACCESS)","Standards":"EN 60947-4 IEC 60947-4","description":"TeSys standard contactor - 2 poles - 200 A - coil 220 V DC","Product name":"TeSys B","lifecycle_stage":"current","Shock resistance":"4 gn 2 gn","Device short name":"CV1BG","Poles description":"2P","Operating altitude":"6561.68 ft (2000 m)","Control circuit type":"DC","Utilisation category":"AC-3 AC-1","Vibration resistance":"4 gn 2 gn","Contactor application":"Resistive circuits, heating, lighting Motor","Mechanical durability":"5000000 cycles","Maximum operating rate":"120 cyc/mn 131 °F (55 °C)","Connections - terminals":"Control circuit cable with lug Control circuit cable connector","IP degree of protection":"IP00IEC 60529","Pole contact composition":"2 NO","Product or Component Type":"Contactor","[Uc] control circuit voltage":"220 V DC","[Ui] rated insulation voltage":"690 V IEC 60947-4","Control circuit voltage limits":"Operational: 0.85...1.1 Uc (at Drop-out: 0.1...0.65 Uc (at <131 °F (55 °C))","[Ie] rated operational current":"200 A AC for power circuit","[Ue] rated operational voltage":"690 V AC","Current rating code of contactor":"BG","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"23...131 °F (-5...55 °C)","[Ith] conventional free air thermal current":"200 A (at 104 °F (40 °C)) for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7b357134721c591991655b5cb56ee979.pdf","sourceUrl":"https://www.se.com/nl/en/product/CV1BG2G0ZMD00/tesys-standard-contactor-2-poles-200-a-coil-220-v-dc/"},"ai":{"faq":[{"question":"What is the closest alternative to CV1BG2G0ZMD00 in this family?","answer":"Within the TeSys B range, the closest sibling would be a different coil voltage variant — same 200 A 2-pole frame, same AC-1/AC-3 ratings, just a different control circuit voltage. No pin-compatible drop-in exists outside that coil change; the mechanical footprint is shared across the BG current rating code."},{"question":"What compliance documentation is available for this contactor?","answer":"It is certified to EN 60947-4 and IEC 60947-4. Standard Schneider documentation includes the declaration of conformity covering these standards. RoHS and REACH compliance is standard for current-production TeSys parts, though the specific compliance declarations should be pulled from the Schneider product documentation portal."},{"question":"What are the key ratings I need to know?","answer":"200 A rated operational current (AC-1/AC-3) at 690 V AC, 220 V DC coil, 2-pole NO configuration, IP00, 5 million mechanical cycles, operating temperature -5 to 55 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/CV1BG2G0ZMD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/CV1BG2G0ZMD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}