{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"DF223C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"DF223C","canonicalUrl":"https://aoctrl.com/schneider/DF223C","factsUrl":"https://aoctrl.com/api/mcp/products/DF223C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys DF 3-pole fuse carrier, DF223C, rated 125 A at 690 V AC/DC, 22 x 58 mm fuse size, 120 kA SCCR at 400 V.","salesMarkdown":"## Ratings that matter for coordination The DF223C: The 120 kA short-circuit withstand at 400 V per IEC 60947-3 is the number to take into selectivity studies — it clears high fault currents when paired with gG fuse links up to 125 A or aM types. Rated impulse withstand is 8 kV, and the operational voltage covers both AC and DC circuits up to 690 V. Ambient derating starts above 20 °C; full 125 A is available up to that point. Snaps onto 35 mm symmetrical DIN rail, vertical ±23° orientation allowed. Screw-clamp terminals accept 2.5 to 35 mm² solid or flexible (ferruled) conductors; tighten to 4 Nm. The IP20 finger-safe enclosure means it's serviceable without additional shrouding as long as the panel door is closed. ## Compliance documentation Meets EN/IEC 60947-3 for switch-disconnectors, EN/IEC 60269-2 for fuse bases, and UL 4248-1 / CSA C22.2 No 4248-1. Glow-wire tested to 960 °C per IEC 60695-2-1. RoHS and REACH declarations are available with the shipment.","metaTitle":"Schneider DF223C TeSys DF 3P Fuse Carrier, 125 A, 690 V","metaDescription":"Active 3-pole fuse carrier rated 125 A at 690 V AC/DC with 120 kA SCCR at 400 V. Accepts 22x58 mm fuse links. Certified IEC/UL/CSA. Source to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"3.01 in (76.5 mm)","Range":"TeSys","Width":"4.1 in (105 mm)","Height":"5.02 in (127.5 mm)","Category":"US10CP121714","Fuse size":"22 x 58 mm","Fuse type":"0...100 A, gG 0...125 A, aM","Standards":"EN/IEC 60947-3 EN/IEC 60269-2 UL 4248-1 CSA C22.2 No 4248-1","Control type":"Toggle","Product name":"TeSys DF","Fire resistance":"1760 °F (960 °C) IEC 60695-2-1","lifecycle_stage":"current","Mounting Support":"35 mm symmetrical DIN rail","Quantity per Set":"Set of 2","Device short name":"DF22","Mounting position":"Vertical +/- 23°)","Poles description":"3P","Tightening torque":"35.4 lbf.in (4 N.m)","Compatibility code":"DF22","Protective treatment":"TH","Nbr. of units in pkg.":"1","Connections - terminals":"screw clamp terminals 1 0.004...0.05 in² (2.5...35 mm²)rigid screw clamp terminals 2 0.004...0.04 in² (2.5...25 mm²)rigid screw clamp terminals 1 0.004...0.05 in² (2.5...35 mm²)flexible with or without screw clamp terminals 2 0.004...0.04 in² (2.5...25 mm²)flexible with or without","IP degree of protection":"IP20 conforming to IEC 60529","Short-circuit withstand":"120 kA 400 V IEC 60947-3 120 kA 500 V IEC 60947-3 80 kA 690 V IEC 60947-3","Product or Component Type":"Fuse carrier","[Ui] rated insulation voltage":"690 V AC","[Ie] rated operational current":"125 A","[Ue] rated operational voltage":"690 V AC 690 V DC","[Ipk] rated peak withstand current":"19 kA with tubular links IEC 60269-1","Ambient air temperature for storage":"-40...176 °F (-40...80 °C)","Ambient air temperature for operation":"-4...140 °F (-20...60 °C) with derating above 20°C","[Uimp] rated impulse withstand voltage":"8 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$26.75","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f4b5b2865dbb8b6e3c55d6a4a9ab6334.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/DF223C/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of DF223C?","answer":"The listed depth is 3.01 inches (76.5 mm)."},{"question":"What range does the DF223C belong to?","answer":"It is part of the TeSys range from Schneider Electric."},{"question":"What compliance documentation does Schneider provide for DF223C?","answer":"The holder is certified to EN/IEC 60947-3, EN/IEC 60269-2, UL 4248-1, and CSA C22.2 No 4248-1. It also meets glow-wire test at 960 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/DF223C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/DF223C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}