{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"DPE50B7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"DPE50B7","canonicalUrl":"https://aoctrl.com/schneider/DPE50B7","factsUrl":"https://aoctrl.com/api/mcp/products/DPE50B7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys DPE contactor, DPE50B7, 50 A, 3-pole, 30 HP at 480 V AC, 24 V AC 50/60 Hz coil, screw terminals, rail/plate mount.","salesMarkdown":"The DPE50B7: The 50 A rating (AC-1/AC-3) is the headline — it tells you this contactor can carry 50 A continuously in resistive duty and switch motor loads up to that current. For motor applications, the real selection number is the horsepower table: 30 HP at 460/480 V AC three-phase, or 10 HP at 230 V. The insulation voltage (Ui) is rated 690 V per IEC 60947-4-1, so it's comfortable on 480 V systems with margin. The 24 V AC coil draws from a control transformer; verify the coil's inrush doesn't exceed your PLC output or relay rating. Mounts on a rail or plate (Mounting Support: Rail Plate). Dimensions are 4.8 x 2.2 x 4.8 inches (122 x 55 x 122 mm) — fits a standard panel footprint. Power circuit terminals accept screw connections for 2.5 to 25 mm² flexible or solid wire, with separate torque specs for larger (7 N·m) and smaller (5 N·m) conductors. Control circuit terminals are screw clamp, 1 to 4 mm². No special tools beyond a Pozidriv #2 or flat 6 mm driver.","metaTitle":"Schneider Electric DPE50B7 Easy TeSys Contactor, 50A 3P, 30H","metaDescription":"Schneider Electric DPE50B7 Easy TeSys contactor, 50 A, 3 poles, 30 HP at 480 V AC, 24 V AC 50/60 Hz coil. Active production, UL/CSA/IEC certified, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Depth":"4.8 in (122 mm)","Range":"Easy TeSys","Width":"2.2 in (55 mm)","title":"DPE50B7","Height":"4.8 in (122 mm)","Category":"US10I1222329","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1","description":"IEC contactor,Easy TeSys DPE,nonreversing,50A,3P,30HP at 480V AC,24V AC 50/60Hz coil","Product name":"Easy TeSys DPE","lifecycle_stage":"current","Mounting Support":"Rail Plate","Device short name":"DPE","Poles description":"3P","Tightening torque":"Power circuit 62.0 lbf.in (7 N.m) screw connectors 0.02...0.04 in² (16...25 mm²) hexagonal 0.2 in (4 mm) Power circuit 44.3 lbf.in (5 N.m) screw connectors 0.004...0.02 in² (2.5...16 mm²) hexagonal 0.2 in (4 mm) Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2 Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2","Climatic withstand":"IACS E10 IEC 60947-1 Annex Q category D","Operating altitude":"0...6561.68 ft (0...2000 m)","Utilisation category":"AC-1 AC-3","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor open 10 Gn for 11 ms) Shocks contactor closed 15 Gn for 11 ms)","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit: screw connection 1 0.004...0.04 in² (2.5...25 mm²) - cable stiffness: flexible without cable end Power circuit: screw connection 2 0.004...0.02 in² (2.5...16 mm²) - cable stiffness: flexible without cable end Power circuit: screw connection 1 0.004...0.04 in² (2.5...25 mm²) - cable stiffness: flexible with cable end Power circuit: screw connection 2 0.004...0.02 in² (2.5...10 mm²) - cable stiffness: flexible with cable end Power circuit: screw connection 1 0.004...0.04 in² (2.5...25 mm²) - cable stiffness: solid without cable end Power circuit: screw connection 2 0.004...0.02 in² (2.5...16 mm²) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end","Pole contact composition":"3 NO","Product or Component Type":"Contactor","Signalling circuit frequency":"25...400 Hz","Ambient Air Temperature for Storage":"-76...176 °F (-60...80 °C)","Ambient Air Temperature for Operation":"-40...140 °F (-40...60 °C)","Motor power HP (Conforming to UL,CSA)":"3 hp at 115 V AC 50/60 Hz for 1 phase motors 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors 10 hp at 200/208 V AC 50/60 Hz for 3 phase motors 10 hp at 230/240 V AC 50/60 Hz for 3 phase motors 30 hp at 460/480 V AC 50/60 Hz for 3 phase motors 30 hp at 575/600 V AC 50/60 Hz for 3 phase motors","Flame resistance (Conforming to UL,CSA)":"V1 conforming to UL 94","[Ui] rated insulation voltage (Conforming to UL,CSA)":"Power circuit 690 V IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$95.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/322b8cfc34ac980b7b75a6089c0bb6c7.pdf","sourceUrl":"https://www.se.com/us/en/product/DPE50B7/iec-contactoreasy-tesys-dpenonreversing50a3p30hp-at-480v-ac24v-ac-50-60hz-coil/"},"ai":{"faq":[{"question":"What are the key ratings of the DPE50B7?","answer":"50 A rated current in AC-1/AC-3, 30 HP at 480 V AC three-phase, 24 V AC 50/60 Hz coil, 3 poles, insulation voltage 690 V, screw terminals, rail/plate mount."},{"question":"What certifications does the DPE50B7 carry?","answer":"UL 60947-4-1, CSA C22.2 No 14, EN/IEC 60947-4-1 and 60947-5-1. Flame resistance V1 per UL 94."},{"question":"What is the mounting and wiring requirement?","answer":"Mounts on rail or plate. Power circuit screw terminals accept 2.5–25 mm² wire; control circuit screw clamp terminals accept 1–4 mm². Torque: power circuit up to 7 N·m, control circuit 1.7 N·m."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/DPE50B7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/DPE50B7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}