{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"E5CC-QQ3A5M-003","brand":"Omron","brandSlug":"omron","productSlug":"E5CC-QQ3A5M-003","canonicalUrl":"https://aoctrl.com/omron/E5CC-QQ3A5M-003","factsUrl":"https://aoctrl.com/api/mcp/products/E5CC-QQ3A5M-003","rawCanonicalId":null},"summary":{"shortDescription":"Omron E5CC series, Process / Temperature Controller, PID control, relay (3) + voltage (external SSR) (2) outputs, RS-485 CompoWay/F Modbus, 100~240VAC, panel mount, IP66 front, screw terminals.","salesMarkdown":"## Panel cutout and wiring decision The Omron E5CC-QQ3A5M-003 is a 1/16 DIN process and temperature controller that fits a standard 45.00 mm x 45.00 mm square panel cutout. The screw-terminal termination means no special crimp tooling on the line — strip and torque to the terminal block. It accepts universal inputs: RTD (Pt100), thermocouple types B, E, J, K, L, N, PLII, R, S, T, U, W, plus 0~20 mA and 0~10 VDC process signals. That range covers -200°C to 2300°C, so one part number handles furnace thermocouples and chilled-water RTDs without a separate signal conditioner. ## Outputs and control loop Three relay outputs handle alarm, event, or auxiliary control, and two voltage-pulse outputs drive external SSRs for the heating and cooling legs. That split is typical for a dual-loop or heat-cool application where the relays carry the on/off events and the SSR outputs modulate the power elements. Control method is selectable between on/off and proportional (PID). The PID autotune is standard on the E5CC series — the controller learns the process dynamics on first run and sets gains without a manual Ziegler-Nichols calculation. ## Fieldbus and diagnostics RS-485 communications support both Omron CompoWay/F and Modbus RTU protocols. That means it drops into a Modbus RTU network directly — no gateway or protocol converter needed between the controller and the PLC. The heater fault detection feature monitors current draw on the load and flags a broken heater or SSR short. On an oven or extruder barrel, that alarm prevents a cold zone from going unnoticed until the product is scrap. The dual-color LCD backlight shows four characters per row in two rows, with the main PV in 0.600\" digits and the SV in 0.280\" digits — readable from across a panel. The IP66-rated front panel withstands washdown splashes and dust ingress, so it suits food-and-beverage or pharmaceutical panel environments where a standard IP54 controller would need a separate cover. Sourced to order against the BOM quantity.","metaTitle":"Omron E5CC-QQ3A5M-003 Temperature Controller, PID, RS-485","metaDescription":"Omron E5CC-QQ3A5M-003 process/temperature controller. PID control, relay + voltage (SSR) outputs, RS-485 Modbus, IP66 front.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Series":"E5CC","Weight":"0.265 lb (120.2 g)","Package":"Box","Mounting":"Panel Mount","IP Rating":"IP66","Output Type":"Relay (3), Voltage (External SSR) (2)","Protocol":"RS-485 (CompoWay/F, Modbus)","Control Method":"On/Off, Proportional (PID)","Product Status":"Active","Supply Voltage":"100 to 240VAC","Temp Operating Max":"55 °C","Temp Operating Min":"-10 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c6d2565f7c49acd020a74c22dc4212b3.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/E5CC-QQ3A5M-003/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/omron/E5CC-QQ3A5M-003","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/E5CC-QQ3A5M-003 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}