{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"E5CC-QX2DBM-001","brand":"Omron","brandSlug":"omron","productSlug":"E5CC-QX2DBM-001","canonicalUrl":"https://aoctrl.com/omron/E5CC-QX2DBM-001","factsUrl":"https://aoctrl.com/api/mcp/products/E5CC-QX2DBM-001","rawCanonicalId":null},"summary":{"shortDescription":"Omron E5CC Series process temperature controller, 24VAC/DC, dual relay plus voltage (external SSR) output, spring terminal termination, IP66 front panel, heater fault detection.","salesMarkdown":"The Omron E5CC-QX2DBM-001 is a 1/16 DIN panel-mount process temperature controller accepting universal inputs — RTD (Pt100), thermocouple types B, E, J, K, L, N, PLII, R, S, T, U, W, plus 0–20 mA or 0–10 VDC linear signals — so it covers most industrial temperature sensing without needing a separate signal conditioner. Outputs are two relay contacts plus a voltage pulse for driving an external SSR, giving you a dedicated heater drive channel and a separate alarm or event output on the relays. Power it from 24 VAC or 24 VDC — common in control panels where a single 24 V supply feeds the PLC and panel instruments — and the spring-cage terminals accept 0.2–2.5 mm² solid or ferruled stranded without needing a screwdriver torque check. ## What the IP66 rating means on a panel-mount controller The IP66 front-panel seal means the controller withstands hose-down cleaning and condensation — suitable for food-processing, washdown, or outdoor enclosures where a standard IP20 front would let moisture into the display cavity. The square 45.00 mm x 45.00 mm panel cutout is the standard 1/16 DIN footprint; it drops into existing punch-outs without adapter plates. ## Heater fault detection built in The integrated heater fault detection monitors current draw on the load side and flags a broken heater or SSR short — a feature that normally requires an external current transformer and alarm module on simpler controllers. Control method is selectable between on/off and full PID with auto-tune, so you can commission it as a simple limit controller or let it self-tune for a closed-loop process.","metaTitle":"Omron E5CC-QX2DBM-001 Temperature Controller, 24VAC/DC","metaDescription":"Omron E5CC-QX2DBM-001 process temperature controller. 24VAC/DC supply, dual relay + voltage (SSR) output, IP66 front panel, spring terminals.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Process / Temperature Controllers"],"specifications":{"Type":"Process, Temperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)","title":"E5CC-QX2DBM-001","Series":"E5CC","Weight":"0.265 lb (120.2 g)","Package":"Box","Features":"Heater Fault Detection","Input Range":"-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC","Output Type":"Relay (2), Voltage (External SSR)","description":"CONTROL TEMP RELAY/VOLT OUT 24V","Display Type":"LCD - Dual Color Characters, Backlight","Mounting Type":"Panel Mount","Control Method":"On/Off, Proportional (PID)","lifecycle_stage":"current","Voltage - Supply":"24VAC/DC","Termination Style":"Spring Terminal","Ingress Protection":"IP66 - Dust Tight, Water Resistant","Operating Temperature":"-10°C ~ 55°C","Panel Cutout Dimensions":"Square - 45.00mm x 45.00mm","Display Characters - Height":"0.600\" (15.20mm), 0.280\" (7.10mm)","Number of Characters Per Row":"4, 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c6d2565f7c49acd020a74c22dc4212b3.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What type of output does E5CC-QX2DBM-001 provide?","answer":"The E5CC-QX2DBM-001 provides two relay outputs and one voltage pulse output for driving an external solid-state relay (SSR). The relay contacts handle alarm or event switching; the voltage output is the main control signal for a heater SSR."},{"question":"Can E5CC-QX2DBM-001 be used with a PT100 RTD?","answer":"Yes. The controller accepts RTD inputs including Pt100, along with thermocouple types B, E, J, K, L, N, PLII, R, S, T, U, W, and linear 0–20 mA or 0–10 VDC signals. The input range spans -200°C to 2300°C depending on sensor type."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/omron/E5CC-QX2DBM-001","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/E5CC-QX2DBM-001 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}