{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"E5CC-TRX3A5M-000","brand":"Omron","brandSlug":"omron","productSlug":"E5CC-TRX3A5M-000","canonicalUrl":"https://aoctrl.com/omron/E5CC-TRX3A5M-000","factsUrl":"https://aoctrl.com/api/mcp/products/E5CC-TRX3A5M-000","rawCanonicalId":null},"summary":{"shortDescription":"Omron E5CC-T series process/temperature controller, 100-240VAC supply, 4 relay outputs, PID/On-Off control, universal input for RTD/thermocouple/analog, IP66 front panel, 45x45mm panel cutout.","salesMarkdown":"## Panel fit and control capability The Omron E5CC-TRX3A5M-000 is a 1/16 DIN panel-mount process and temperature controller that accepts a broad range of sensor inputs — RTD, thermocouple types B, E, J, K, L, N, PLII, R, S, T, U, W, plus 0-20 mA and 0-10 VDC analog signals — covering everything from cryogenic -200°C up to 2300°C furnace work. Four dedicated relay outputs give you independent control, alarm, or event channels without needing external interposing relays for most loads. The dual-color LCD backlight shows two rows of four characters each, letting you read process value and setpoint simultaneously. Control method is selectable between on/off and full PID with auto-tuning — the PID loop handles most thermal processes (ovens, extruders, packaging seal bars) without an external programmer. The IP66-rated front panel means the controller face withstands washdown and splash — suitable for food-processing or beverage lines where a standard IP54 front would fail. The screw-terminal rear connection is field-serviceable but takes up more depth than a spring-clamp variant. Universal AC supply (100-240 VAC) eliminates the need to stock separate 110V and 220V SKUs. The 45x45 mm square cutout is the standard 1/16 DIN footprint, so it retrofits directly into existing panel holes from Omron E5CS or similar 1/16 DIN controllers.","metaTitle":"Omron E5CC-TRX3A5M-000 Temperature Controller","metaDescription":"Omron E5CC-TRX3A5M-000 process controller with 4 relay outputs, PID control, universal input (RTD/TC/analog), IP66 front, 100-240VAC. Active, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Process / Temperature Controllers"],"specifications":{"Type":"Process, Temperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)","Series":"E5CC-T","Weight":"0.265 lb (120.2 g)","Package":"Bulk","Input Range":"-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC","Output Type":"Relay (4)","Display Type":"LCD - Dual Color Characters, Backlight","Mounting Type":"Panel Mount","Control Method":"On/Off, Proportional (PID)","lifecycle_stage":"current","Voltage - Supply":"100 ~ 240VAC","Termination Style":"Screw Terminal","Ingress Protection":"IP66 - Dust Tight, Water Resistant","Operating Temperature":"-10°C~55°C","Panel Cutout Dimensions":"Square - 45.00mm x 45.00mm","Display Characters - Height":"0.600\" (15.20mm), 0.280\" (7.10mm)","Number of Characters Per Row":"4, 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c6d2565f7c49acd020a74c22dc4212b3.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/E5CC-TRX3A5M-000/alternatives.json"},"ai":{"faq":[{"question":"Is the E5CC-TRX3A5M-000 compatible with a Type K thermocouple?","answer":"Yes. The E5CC-TRX3A5M-000 accepts Type K thermocouple inputs as part of its universal input range, which covers types B, E, J, K, L, N, PLII, R, S, T, U, and W, plus RTD and analog signals."},{"question":"What is the input range of the E5CC-TRX3A5M-000?","answer":"The input range spans -200°C to 2300°C for thermocouple/RTD, plus 0-20 mA and 0-10 VDC analog signals. The actual usable range depends on the sensor type selected."},{"question":"What replaces the E5CC-TRX3A5M-000 if I need RS-485 communications?","answer":"The E5CC-TRX3A5M-003 is the functionally closest variant — it adds RS-485 (CompoWay/F, Modbus) communication and heater fault detection while keeping the same 4-relay output configuration, universal input, and IP66 front panel."},{"question":"How do I set PID parameters on the E5CC-TRX3A5M-000?","answer":"The controller supports on/off and proportional PID control with auto-tuning. PID parameters (proportional band, integral time, derivative time) are set through the front-panel menu; auto-tune initiates a self-tuning cycle that calculates values based on the process response."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/omron/E5CC-TRX3A5M-000","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/E5CC-TRX3A5M-000 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}