{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"E5EC-TRR4A5M-010","brand":"Omron","brandSlug":"omron","productSlug":"E5EC-TRR4A5M-010","canonicalUrl":"https://aoctrl.com/omron/E5EC-TRR4A5M-010","factsUrl":"https://aoctrl.com/api/mcp/products/E5EC-TRR4A5M-010","rawCanonicalId":null},"summary":{"shortDescription":"Omron E5EC-T series, E5EC-TRR4A5M-010 Process/Temperature Controller, RTD and 13 thermocouple types, 6 relay outputs, PID control, 100-240 VAC, IP66 front panel, screw terminal.","salesMarkdown":"## Six relay outputs for multi-zone or cascade control The E5EC-TRR4A5M-010 packs six relay outputs in a single 92 mm x 45 mm panel cutout — enough for a heating/cooling pair plus four alarm or event relays without adding a slave controller. The relay bank handles discrete on/off or time-proportioned PID outputs, so a single part covers both the control loop and the supervisory annunciation. ## Wide sensor input range covers most process signals Accepts RTD and 13 thermocouple types (B, E, J, K, L, N, PLII, R, S, T, U, W) spanning -200°C to 2300°C, plus 0-20 mA and 0-10 VDC process inputs — one controller for temperature or linear transducers. The tri-color LCD displays up to three process values simultaneously (4 characters per row), useful for showing PV, SV, and heater current or deviation. ## Active production — no last-time-buy pressure Sourced through independent distribution; availability and current pricing confirmed at RFQ against the BOM quantity. ## IP66 front panel survives washdown environments The IP66-rated front panel keeps washdown water and dust out of the enclosure when the gasket is seated against the panel cutout. Suitable for food-and-beverage or pharmaceutical lines where hose-down cleaning is routine. Screw-terminal connections simplify field wiring — no special crimp tooling or ferrule kits needed for the control cabinet. ## Event input and heater fault detection built in The event input can trigger a setpoint change, auto-tuning start, or alarm mask from an external dry contact — useful for recipe switching or interlocking with a safety circuit. Heater fault detection monitors current draw on the heater loop and flags a broken element or SSR short before the process drifts out of tolerance.","metaTitle":"Omron E5EC-TRR4A5M-010 Process/Temp Controller","metaDescription":"Omron E5EC-TRR4A5M-010 process/temperature controller, 6 relay outputs, PID control, IP66 front. Active production. Quoted to order against BOM.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Process / Temperature Controllers"],"specifications":{"Type":"Process, Temperature Controller (RTD, Type B, E, J, K, L, N, PLII, R, S, T, U, W)","Series":"E5EC-T","Weight":"0.463 lb (210.01 g)","Package":"Bulk","Features":"Event Input, Heater Fault Detection","Input Range":"-200°C ~ 2300°C, 0 ~ 20mA, 0 ~ 10VDC","Output Type":"Relay (6)","Display Type":"LCD - Tri Color Characters, Backlight","Mounting Type":"Panel Mount","Control Method":"On/Off, Proportional (PID)","lifecycle_stage":"current","Voltage - Supply":"100 ~ 240VAC","Termination Style":"Screw Terminal","Ingress Protection":"IP66 - Dust Tight, Water Resistant","Operating Temperature":"-10°C ~ 55°C","Panel Cutout Dimensions":"Rectangular - 92.00mm x 45.00mm","Display Characters - Height":"0.710\" (18.00mm), 0.433\" (11.00mm), 0.307\" (7.80mm)","Number of Characters Per Row":"4, 4, 4"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c6d2565f7c49acd020a74c22dc4212b3.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/E5EC-TRR4A5M-010/alternatives.json"},"ai":{"faq":[{"question":"Will E5EC-TRR4A5M-010 drop into a panel cut out for E5EC-TRR4A5M-008 without rewiring?","answer":"Yes — both share the same 92.00 mm x 45.00 mm rectangular panel cutout, same screw-terminal termination, and same 100-240 VAC supply. The only functional difference is that the -008 adds RS-485 communications (CompoWay/F, Modbus); the -010 omits the serial port. If your application does not need serial networking, the -010 is a direct mechanical and electrical swap."},{"question":"What is the E5EC-TRR4A5M-010's input range and supported sensor types?","answer":"It accepts RTD and 13 thermocouple types (B, E, J, K, L, N, PLII, R, S, T, U, W) from -200°C to 2300°C, plus 0-20 mA and 0-10 VDC process signals. This covers most industrial temperature and linear transducer applications in a single controller."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/omron/E5EC-TRR4A5M-010","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/E5EC-TRR4A5M-010 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}