{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW12701","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW12701","canonicalUrl":"https://aoctrl.com/schneider/ENW12701","factsUrl":"https://aoctrl.com/api/mcp/products/ENW12701","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, Trip System 6.0s control unit, LSIG protection, 630…6300 A, 690 V AC, 50/60 Hz, IEC 60947-2.","salesMarkdown":"The Schneider Electric ENW12701 is a Trip System 6.0s control unit for the EasyPact NW range of air circuit breakers. It provides LSIG protection — overload (long-time), short-time short-circuit, instantaneous short-circuit, and earth fault — via a microprocessor-based trip unit rated 630…6300 A. That means it coordinates with the breaker's interrupting capacity under fault conditions up to that voltage. ## Protection and adjustment detail Long-time pick-up (Ir) adjusts from 0.4 to 1 x In in 10 steps, with a delay (Tr) from 0.5 to 24 s at 6 x Ir (accuracy 0 to -20 %). Short-time pick-up (Isd) also offers 10 settings, delay (Tsd) from 100 to 600 ms. Instantaneous pick-up (Ii) covers 2 to 15 x In, accuracy ±10 %, also adjustable in 10 steps. Ground-fault pick-up has 10 settings. Thermal memory is included, so the trip unit accounts for prior heating when re-energizing after a trip — critical for motor and transformer feeders where repeated overloads degrade insulation faster than a single event. ## Physical integration and connectivity Dimensions: 200 mm high, 58 mm wide, 77 mm deep. Fixed mounting mode. The neutral position is left; pole configurations available are 4P and 3P, with protected poles configurable as 3D, 3D + N/2, or 4D. Neutral protection can be set to without protection (3D), 0.5 x Ir (3D + N/2), or 1 x Ir (4D). Communication via NFC wireless peer-to-peer and USB Type-C interface. Status is indicated by a green, red, and orange health status bar plus a green ready LED. Fault indication covers short-circuit, overload, earth fault, and internal fault. Control button is a single I button with LED indication. Data recording includes alarm logs, event logs, and trip logs — useful for post-event analysis without needing external software. Battery type is lithium non-rechargeable, which powers the trip unit's memory and clock during de-energized periods. This control unit is designed for industrial standard circuit breaker applications. It is a component of the EasyPact NW family, which covers air breakers from 630 A up to 6300 A.","metaTitle":"Schneider Electric ENW12701 EasyPact NW Trip System 6.0s, LS","metaDescription":"Schneider Electric ENW12701 EasyPact NW Trip System 6.0s control unit. LSIG protection, 630-6300 A, 690 V AC, IEC 60947-2. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"77 mm","Width":"58 mm","Height":"200 mm","Status LED":"With green, red and orange health status bar With green ready","Battery type":"Lithium non-rechargeable","Network type":"AC","Mounting mode":"Fixed","Data recording":"Alarm logs Event logs Trip logs","Thermal memory":"Yes","Trip unit name":"Trip System 6.0s","Protection type":"Overload protection (long time) Short time short-circuit protection Earth fault Instantaneous short-circuit protection","lifecycle_stage":"current","Fault indication":"Short-circuit Overload Earth fault Internal fault","Neutral position":"Left","Range of product":"EasyPact NW","Trip unit rating":"630...6300 A","Network frequency":"50/60 Hz","Poles description":"4P 3P","Control Button Type":"I button","With LED indication":"True","Trip unit technology":"Micro-processor based","Product or component type":"Control unit","Neutral protection setting":"Without protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)","Circuit breaker application":"Industrial Standard","Communication port protocol":"NFC network: wireless interface: peer to peer USB network: Type-C interface: peer to peer","Protected poles description":"3D + N/2 4D 3D","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 10 settings","Short-time delay adjustment type":"Adjustable 11 settings","Long time pick-up adjustment range":"0.4...1 x In Off","Ambient air temperature for storage":"-40...85 °C","Ground-fault pick-up adjustment type":"Adjustable 10 settings","Long time pick-up adjustment type Ir":"Adjustable 10 settings","Ambient air temperature for operation":"-25...70 °C","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s (6 x Ir), accuracy: 0...- 20 %","Instantaneous pick-up adjustment range":"2...15 x In, accuracy: +/- 10 % Off","Short-time pick-up adjustment type Isd":"Adjustable 10 settings","[Tsd] Short-Time Delay Adjustment Range":"100...600 ms","Instantaneous pick-up adjustment type Ii":"Adjustable 10 settings","[Isd] short-time pick-up adjustment range":"1.5...10 x Ir","[Ig] ground-fault pick-up adjustment range":"0.2...1 x In (In < 3200 A), accuracy: +/- 10 % 500...1 x In (In > 400 A), accuracy: +/- 10 %","Ground-fault time delay adjustment type -tg":"Adjustable 14 settings","[Tg] Ground-Fault Time Delay Adjustment Range":"100...1000 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6d212e499119730951a2d05e8624262f.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW12701/trip-unit-easypact-nw-trip-system-6-0s-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW12701/alternatives.json"},"ai":{"faq":[{"question":"What are the key protection functions of ENW12701?","answer":"The ENW12701 Trip System 6.0s provides LSIG protection: overload (long-time), short-time short-circuit, instantaneous short-circuit, and earth fault. It is microprocessor-based with fully adjustable settings."},{"question":"What is the voltage and standard rating for ENW12701?","answer":"Rated operational voltage is 690 V AC at 50/60 Hz, conforming to IEC 60947-2."},{"question":"Where can I buy ENW12701?","answer":"The ENW12701 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW12701","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW12701 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}