{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW12702","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW12702","canonicalUrl":"https://aoctrl.com/schneider/ENW12702","factsUrl":"https://aoctrl.com/api/mcp/products/ENW12702","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, Trip System 6.0s microprocessor-based control unit, LSIG protection, 630–6300 A, 690 V AC IEC 60947-2, drawout mount, 77 x 58 x 200 mm.","salesMarkdown":"## What this trip unit does The ENW12702 is a microprocessor-based control unit for the Schneider Electric EasyPact NW range of air circuit breakers. It provides LSIG protection — overload (long-time), short-time short-circuit, instantaneous short-circuit, and earth fault — adjustable across ten settings per function. The trip unit rating spans 630 to 6300 A, and it operates at 690 V AC 50/60 Hz, certified to IEC 60947-2. That means it can be dialled in for everything from a 630 A feeder to a 6300 A main, with selectivity coordination possible across the full band. Drawout mount for frame 1 — pulls out without unbolting busbars, which is the kind of detail a field-service tech appreciates when the line is down and every minute counts. Dimensions are 77 mm deep, 58 mm wide, 200 mm tall, fitting the standard EasyPact NW cradle. Neutral position is left; poles configurable as 3P or 4P with neutral protection settings (3D, 3D+N/2, 4D). ## Adjustments and diagnostics Long-time pickup (Ir) adjustable 0.4–1 x In with ten settings; short-time pickup (Isd) also ten settings; instantaneous (Ii) adjustable 2–15 x In, also ten settings. Ground-fault pickup has its own ten settings. The long-time delay (Tr) spans 0.5–24 s at 6 x Ir with 0 to –20% accuracy; short-time delay (Tsd) is 100–600 ms. Thermal memory is included, so the unit remembers prior heating — essential for motor feeders or repeated reclosure scenarios. Data recording covers alarm, event, and trip logs, and the status LED shows green, red, and orange health bars plus a green ready indicator. Fault indication flags short-circuit, overload, earth fault, and internal fault. ## Communications and power Onboard NFC and USB Type-C for peer-to-peer wireless interface — no special dongle needed; a smartphone app can pull trip logs or adjust settings. Battery is lithium non-rechargeable, which backs the clock and event logs during a power loss. Network type is AC, 50/60 Hz.","metaTitle":"Schneider Electric ENW12702 EasyPact NW Trip Unit, LSIG, 630","metaDescription":"Schneider Electric ENW12702 EasyPact NW microprocessor-based control unit. LSIG protection, 630–6300 A, 690 V AC IEC 60947-2. In current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"77 mm","Width":"58 mm","Height":"200 mm","Status LED":"With green, red and orange health status bar With green ready","Battery type":"Lithium non-rechargeable","Network type":"AC","Mounting mode":"Drawout for frame 1","Data recording":"Alarm logs Event logs Trip logs","Thermal memory":"Yes","Trip unit name":"Trip System 6.0s","Protection type":"Overload protection (long time) Short time short-circuit protection Earth fault Instantaneous short-circuit protection","lifecycle_stage":"current","Fault indication":"Short-circuit Overload Earth fault Internal fault","Neutral position":"Left","Range of product":"EasyPact NW","Trip unit rating":"630...6300 A","Network frequency":"50/60 Hz","Poles description":"4P 3P","Control Button Type":"I button","With LED indication":"True","Trip unit technology":"Micro-processor based","Product or component type":"Control unit","Neutral protection setting":"Without protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)","Circuit breaker application":"Industrial Standard","Communication port protocol":"NFC network: wireless interface: peer to peer USB network: Type-C interface: peer to peer","Protected poles description":"3D + N/2 4D 3D","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 10 settings","Short-time delay adjustment type":"Adjustable 11 settings","Long time pick-up adjustment range":"0.4...1 x In Off","Ambient air temperature for storage":"-40...85 °C","Ground-fault pick-up adjustment type":"Adjustable 10 settings","Long time pick-up adjustment type Ir":"Adjustable 10 settings","Ambient air temperature for operation":"-25...70 °C","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s (6 x Ir), accuracy: 0...- 20 %","Instantaneous pick-up adjustment range":"2...15 x In, accuracy: +/- 10 % Off","Short-time pick-up adjustment type Isd":"Adjustable 10 settings","[Tsd] Short-Time Delay Adjustment Range":"100...600 ms","Instantaneous pick-up adjustment type Ii":"Adjustable 10 settings","[Isd] short-time pick-up adjustment range":"1.5...10 x Ir","[Ig] ground-fault pick-up adjustment range":"0.2...1 x In (In < 3200 A), accuracy: +/- 10 % 500...1 x In (In > 400 A), accuracy: +/- 10 %","Ground-fault time delay adjustment type -tg":"Adjustable 14 settings","[Tg] Ground-Fault Time Delay Adjustment Range":"100...1000 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cca43308f48cdb409eaa8dd27102598a.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW12702/trip-unit-easypact-nw-trip-system-6-0s-drawout/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW12702/alternatives.json"},"ai":{"faq":[{"question":"What protection functions does the ENW12702 provide?","answer":"It provides LSIG protection: overload (long-time), short-time short-circuit, instantaneous short-circuit, and earth fault, all with multiple adjustable settings."},{"question":"What is the trip unit rating range for ENW12702?","answer":"The trip unit rating is 630 to 6300 A, adjustable via ten settings per protection function."},{"question":"How is the ENW12702 mounted?","answer":"It uses a drawout mount for frame 1, allowing removal without disturbing busbars. Dimensions are 77 mm deep, 58 mm wide, 200 mm tall."},{"question":"What communications interfaces does the ENW12702 have?","answer":"It has NFC and USB Type-C for peer-to-peer wireless interface, plus a lithium battery for backing logs during power loss."},{"question":"Where can I buy ENW12702 and how is it quoted?","answer":"The ENW12702 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW12702","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW12702 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}