{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13201","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13201","canonicalUrl":"https://aoctrl.com/schneider/ENW13201","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13201","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW ENW13201, 3P drawout circuit breaker, 630 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2.","salesMarkdown":"Schneider Electric ENW13201 is a 3-pole drawout circuit breaker from the EasyPact NW family, rated 630 A at 40 °C with a breaking capacity of 66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. ## Drawout mounting and panel integration Mounts on a rail base plate with drawout mechanism — the breaker can be racked out for maintenance or replacement without disturbing the main bus connections. Rear connection terminals accept horizontal or vertical bus bars; connection pitch is 70 mm without a spreader. Overall dimensions are 288 mm wide × 322 mm high × 277 mm deep, so plan for a cutout that accommodates the drawout cradle plus clearance for arc chute venting. Rated for 20,000 mechanical cycles with maintenance (10,000 without) and 5,000 electrical cycles at 440 V AC without maintenance — this is a Category B breaker, meaning it's designed for selective coordination with downstream devices.","metaTitle":"Schneider Electric ENW13201 EasyPact NW Circuit Breaker, 630","metaDescription":"Schneider Electric ENW13201 EasyPact NW drawout circuit breaker, 630 A rated current, 66 kA Icu at 440 V AC, IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"277 mm","Range":"EasyPact","Width":"288 mm","title":"ENW13201","Height":"322 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 3 Poles, 630A, withdrawal","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW06C","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"630 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"630 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d1836c1a0872559801b427738a586f99.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13201/circuit-breaker-frame-adapt-easypact-nw-3-poles-630a-withdrawal/"},"ai":{"faq":[{"question":"Where can I buy ENW13201 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What is ENW13201's breaking capacity at 440 V?","answer":"66 kA Icu (ultimate breaking capacity) and 55 kA Ics (service breaking capacity) at 220...440 V AC 50/60 Hz per IEC 60947-2."},{"question":"What standards does ENW13201 comply with?","answer":"IEC 60947-2 for circuit breakers, with isolation suitability confirmed per that standard. Pollution degree 3 per IEC 60664-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13201","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13201 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}