{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13205","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13205","canonicalUrl":"https://aoctrl.com/schneider/ENW13205","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13205","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, drawout circuit breaker, ENW16C, 1600 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2, 3P.","salesMarkdown":"## What the 1600 A and 66 kA ratings mean for fit The Schneider Electric ENW13205 is an EasyPact NW drawout circuit breaker rated 1600 A at 40 °C with a breaking capacity of 66 kA Icu at 220…440 V AC 50/60 Hz per IEC 60947-2. The rated short-time withstand current Icw is 50 kA for 1 s, which matters for selective coordination downstream — the breaker holds in during a fault long enough for an upstream device to clear. This is a 3-pole, Category B breaker, meaning it's intended for distribution duty with full selectivity capability — not just cable protection. The 1000 V rated insulation voltage and 12 kV impulse withstand confirm it's built for industrial switchgear environments, not light commercial panels. Drawout mounting on a rail base plate means the breaker can be racked out for maintenance without disturbing the bus connections — a standard requirement for main or tie breakers in a switchgear lineup. Mounts on a rail base plate in drawout configuration — the breaker unit slides in and out, leaving the base and power connections fixed. Connection pitch is 70 mm without spreader; rear connections are standard for switchgear bus risers.","metaTitle":"Schneider Electric ENW13205 EasyPact NW Circuit Breaker, 160","metaDescription":"Schneider Electric ENW13205 EasyPact NW drawout circuit breaker, 1600 A rated current, 66 kA Icu at 440 V AC, IEC 60947-2. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"277 mm","Range":"EasyPact","Width":"288 mm","title":"ENW13205","Height":"322 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 3 Poles, 1600A, withdrawal","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW16C","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"1600 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"1600 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5eff0db02f6eb09d66d162e3136d9b86.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13205/circuit-breaker-frame-adapt-easypact-nw-3-poles-1600a-withdrawal/"},"ai":{"faq":[{"question":"What is the ENW13205's breaking capacity at 440 V?","answer":"The ultimate breaking capacity Icu is 66 kA at 220…440 V AC 50/60 Hz per IEC 60947-2. The service breaking capacity Ics is 55 kA at the same voltage."},{"question":"What standards does the ENW13205 comply with?","answer":"It is designed and tested to IEC 60947-2 for circuit breakers, with pollution degree 3 per IEC 60664-1. The suitability for isolation is confirmed per IEC 60947-2."},{"question":"Where can I buy the ENW13205 and what is the lead time?","answer":"The ENW13205 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here, but a quote request will return real-time supply posture."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13205","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13205 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}