{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13209","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13209","canonicalUrl":"https://aoctrl.com/schneider/ENW13209","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13209","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW13209, 3P 630 A circuit breaker, 66 kA Icu at 440 V AC, IEC 60947-2, fixed mount.","salesMarkdown":"The Schneider Electric ENW13209 is a 3-pole EasyPact NW air circuit breaker rated 630 A at 40 °C, built for distribution duty per IEC 60947-2. The 55 kA Ics (service breaking capacity) tells you it can reclose after a fault at that level, not just survive it once. Rated insulation voltage is 1000 V AC, impulse withstand 12 kV, and short-time withstand 50 kA for 1 second — figures a site electrical engineer uses for selectivity studies and coordination with downstream devices. Fixed-mount design on a rail base plate. Dimensions 276 mm wide × 301 mm high × 196 mm deep — the depth figure an MRO storeroom keeper or panel OEM wireman needs for enclosure depth clearance and gland-plate layout. Connection pitch is 70 mm without spreader; rear horizontal or vertical connection positions give flexibility for busbar or cable entry. Category B utilisation means it's designed for distribution with no specific motor-starting duty; electrical durability is 5000 cycles at 440 V without maintenance.","metaTitle":"Schneider Electric ENW13209 EasyPact NW Circuit Breaker, 630","metaDescription":"ENW13209 EasyPact NW 3P 630 A circuit breaker, 66 kA Icu at 440 V AC, IEC 60947-2. Current production, sourced to order. RFQ for availability and pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"196 mm","Width":"276 mm","Height":"301 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP30","Application":"Distribution","Product Status":"Active","Terminal Pitch":"70 mm without spreader","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category B","Mechanical Life Cycles":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/831581c0cd5025c218ce0f7be8ba42fb.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW13209/circuit-breaker-frame-adapt-easypact-nw-3-poles-630a-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13209/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13209","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13209 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}