{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13209","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13209","canonicalUrl":"https://aoctrl.com/schneider/ENW13209","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13209","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW13209, 3P 630 A circuit breaker, 66 kA Icu at 440 V AC, IEC 60947-2, fixed mount.","salesMarkdown":"The Schneider Electric ENW13209 is a 3-pole EasyPact NW air circuit breaker rated 630 A at 40 °C, built for distribution duty per IEC 60947-2. The 55 kA Ics (service breaking capacity) tells you it can reclose after a fault at that level, not just survive it once. Rated insulation voltage is 1000 V AC, impulse withstand 12 kV, and short-time withstand 50 kA for 1 second — figures a site electrical engineer uses for selectivity studies and coordination with downstream devices. Fixed-mount design on a rail base plate. Dimensions 276 mm wide × 301 mm high × 196 mm deep — the depth figure an MRO storeroom keeper or panel OEM wireman needs for enclosure depth clearance and gland-plate layout. Connection pitch is 70 mm without spreader; rear horizontal or vertical connection positions give flexibility for busbar or cable entry. Category B utilisation means it's designed for distribution with no specific motor-starting duty; electrical durability is 5000 cycles at 440 V without maintenance.","metaTitle":"Schneider Electric ENW13209 EasyPact NW Circuit Breaker, 630","metaDescription":"ENW13209 EasyPact NW 3P 630 A circuit breaker, 66 kA Icu at 440 V AC, IEC 60947-2. Current production, sourced to order. RFQ for availability and pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"196 mm","Range":"EasyPact","Width":"276 mm","Height":"301 mm","Standards":"IEC 60947-2","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW06C","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"630 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"630 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/831581c0cd5025c218ce0f7be8ba42fb.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW13209/circuit-breaker-frame-adapt-easypact-nw-3-poles-630a-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13209/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy ENW13209?","answer":"ENW13209 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of ENW13209?","answer":"The rated ultimate breaking capacity (Icu) is 66 kA at 220…440 V AC, with a service breaking capacity (Ics) of 55 kA at the same voltage range, both per IEC 60947-2."},{"question":"What compliance documentation is available for ENW13209?","answer":"The breaker is certified to IEC 60947-2; manufacturer documentation includes the standard declaration of conformity. Specific RoHS, REACH, or UL documentation should be requested at quote time as it varies by production batch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13209","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13209 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}