{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13210","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13210","canonicalUrl":"https://aoctrl.com/schneider/ENW13210","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13210","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW13210, 3-pole fixed circuit breaker, 800 A rated current, 66 kA Icu at 440 V AC, IEC 60947-2.","salesMarkdown":"The ENW13210 is a 3-pole EasyPact NW circuit breaker from Schneider Electric, rated 800 A at 40 °C and carrying a 66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. Category B utilization means it's designed for distribution duty with selective coordination, not just cable protection. Rated insulation voltage (Ui) is 1000 V AC, and impulse withstand (Uimp) is 12 kV, so it's comfortable on 400/480 V systems with decent margin for switching surges. Short-time withstand (Icw) is 50 kA for 1 second — that's the current it can carry without damage during a delayed trip coordination sequence, which is the spec you need when setting up a selective tripping scheme with downstream breakers. That's the standard for unsealed switchgear in factory environments — no special derating needed for typical panel conditions. Fixed mount on a rail base plate, rear-connected. Dimensions are 276 mm wide × 301 mm high × 196 mm deep. Connection pitch is 70 mm without spreader, which is the standard for this frame size — busbar drilling patterns and cable lug spacing should match that centerline.","metaTitle":"Schneider Electric ENW13210 EasyPact NW Circuit Breaker, 800","metaDescription":"Schneider Electric ENW13210 EasyPact NW circuit breaker. 800 A rated current, 66 kA breaking capacity at 440 V AC, IEC 60947-2. 3-pole, fixed mount. Current production. Available t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"196 mm","Range":"EasyPact","Width":"276 mm","title":"ENW13210","Height":"301 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 3 Poles, 800A, fixed","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW08C","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"800 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"800 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0f1036418daa3ed1ac2ef86d80988c5d.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW13210/circuit-breaker-frame-adapt-easypact-nw-3-poles-800a-fixed/"},"ai":{"faq":[{"question":"What is ENW13210's breaking capacity?","answer":"66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2, with a service breaking capacity (Ics) of 55 kA at the same voltage."},{"question":"What standards does ENW13210 comply with?","answer":"IEC 60947-2 for circuit breakers, with pollution degree 3 per IEC 60664-1 and suitability for isolation per IEC 60947-2."},{"question":"Where can I buy ENW13210?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13210","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13210 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}