{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13211","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13211","canonicalUrl":"https://aoctrl.com/schneider/ENW13211","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13211","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, circuit breaker, ENW13211, 3P, 1000 A at 40 °C, 66 kA Icu at 440 V AC, fixed mount, rear connection.","salesMarkdown":"The Schneider Electric ENW13211 is a 3-pole EasyPact NW circuit breaker rated 1000 A at 40 °C, built for distribution duty in AC networks at 50/60 Hz. For selective coordination with downstream gear, the short-time withstand (Icw) is 50 kA for 1 second, and the making capacity (Icm) is 75 kA — both at 220...440 V AC. That's a Category B breaker (utilisation category B), so it's designed for selectivity in distribution, not just cable protection. Fixed mount on a rail base plate — no draw-out cradle here. Connection is rear, horizontal or vertical, with a 70 mm pitch without spreader. The footprint is 276 mm wide by 301 mm tall by 196 mm deep. ## Durability and environmental range Mechanical endurance: 20,000 cycles with maintenance, 10,000 without. Electrical endurance: 5,000 cycles at 440 V AC without maintenance. Max breaking time is 35 ms, max closing time 70 ms. The contact position indicator is fitted — a green/red flag visible on the front so you can confirm open/closed without metering.","metaTitle":"Schneider Electric ENW13211 EasyPact NW Circuit Breaker, 100","metaDescription":"Schneider Electric ENW13211 EasyPact NW circuit breaker, 1000 A rated current, 66 kA Icu at 440 V AC, IEC 60947-2, 3P, fixed mount. Active lifecycle, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"196 mm","Range":"EasyPact","Width":"276 mm","Height":"301 mm","Standards":"IEC 60947-2","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW10C","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"1000 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"1000 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2b42404913b70f55a4cac6c1fb5b25de.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13211/circuit-breaker-frame-adapt-easypact-nw-3-poles-1000a-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13211/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy ENW13211 and how is it quoted?","answer":"ENW13211 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What is the breaking capacity of ENW13211?","answer":"The ultimate breaking capacity (Icu) is 66 kA at 220...440 V AC per IEC 60947-2. The service breaking capacity (Ics) is 55 kA at the same voltage, meaning the breaker remains usable after clearing a fault at that level."},{"question":"What is the closest alternative to ENW13211 in the EasyPact NW family?","answer":"The ENW13211 is the 1000 A, 66 kA Icu variant in the EasyPact NW range. Other ratings in the same family share the same frame size and rear-connection pattern but differ in current and breaking capacity — the choice depends on your fault-current study and load requirements."},{"question":"What compliance documentation does Schneider provide for ENW13211?","answer":"The breaker is certified to IEC 60947-2, with suitability for isolation confirmed per that standard. Pollution degree 3 per IEC 60664-1. Standard documentation includes the IEC declaration of conformity and test certificates; these are available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13211","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13211 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}