{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13211","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13211","canonicalUrl":"https://aoctrl.com/schneider/ENW13211","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13211","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, circuit breaker, ENW13211, 3P, 1000 A at 40 °C, 66 kA Icu at 440 V AC, fixed mount, rear connection.","salesMarkdown":"The Schneider Electric ENW13211 is a 3-pole EasyPact NW circuit breaker rated 1000 A at 40 °C, built for distribution duty in AC networks at 50/60 Hz. For selective coordination with downstream gear, the short-time withstand (Icw) is 50 kA for 1 second, and the making capacity (Icm) is 75 kA — both at 220...440 V AC. That's a Category B breaker (utilisation category B), so it's designed for selectivity in distribution, not just cable protection. Fixed mount on a rail base plate — no draw-out cradle here. Connection is rear, horizontal or vertical, with a 70 mm pitch without spreader. The footprint is 276 mm wide by 301 mm tall by 196 mm deep. ## Durability and environmental range Mechanical endurance: 20,000 cycles with maintenance, 10,000 without. Electrical endurance: 5,000 cycles at 440 V AC without maintenance. Max breaking time is 35 ms, max closing time 70 ms. The contact position indicator is fitted — a green/red flag visible on the front so you can confirm open/closed without metering.","metaTitle":"Schneider Electric ENW13211 EasyPact NW Circuit Breaker, 100","metaDescription":"Schneider Electric ENW13211 EasyPact NW circuit breaker, 1000 A rated current, 66 kA Icu at 440 V AC, IEC 60947-2, 3P, fixed mount. Active lifecycle, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"196 mm","Width":"276 mm","Height":"301 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP30","Application":"Distribution","Product Status":"Active","Terminal Pitch":"70 mm without spreader","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category B","Mechanical Life Cycles":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2b42404913b70f55a4cac6c1fb5b25de.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13211/circuit-breaker-frame-adapt-easypact-nw-3-poles-1000a-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13211/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13211","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13211 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}