{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13212","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13212","canonicalUrl":"https://aoctrl.com/schneider/ENW13212","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13212","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW13212, 3P circuit breaker, 1250 A at 40 °C, 66 kA Icu at 220-440 V AC, IEC 60947-2.","salesMarkdown":"## Selectivity and Coordination Headroom For the site electrical engineer building a selective coordination study: the ENW13212 carries a 50 kA Icw (short-time withstand current for 1 s at 220-440 V AC) and a 75 kA Icm (short-circuit making capacity). The 12 kV Uimp impulse withstand voltage (per IEC 60947-2) confirms insulation coordination at pollution degree 3 (IEC 60664-1) — typical for industrial panels where conductive dust or condensation is present. Maximum breaking time is 35 ms; maximum closing response time is 70 ms. These figures anchor the time-current curve for downstream device coordination. Fixed-mount on a rail base plate, with rear connection and a 70 mm connection pitch without spreader. The 276 mm width × 301 mm height × 196 mm depth footprint fits standard distribution panel compartments. The mechanical durability is 20,000 cycles with maintenance or 10,000 without, per IEC 60947-2; electrical durability is 5,000 cycles at 440 V AC without maintenance.","metaTitle":"Schneider Electric ENW13212 EasyPact NW Circuit Breaker, 125","metaDescription":"Schneider Electric ENW13212 EasyPact NW circuit breaker, 1250 A rated current at 40 °C, 66 kA Icu at 220-440 V AC, IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"196 mm","Width":"276 mm","Height":"301 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP30","Application":"Distribution","Product Status":"Active","Terminal Pitch":"70 mm without spreader","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category B","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e7bf6afdc42d29562414338e8d6a43b0.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW13212/circuit-breaker-frame-adapt-easypact-nw-3-poles-1250a-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13212/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13212","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13212 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}