{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13212","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13212","canonicalUrl":"https://aoctrl.com/schneider/ENW13212","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13212","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW13212, 3P circuit breaker, 1250 A at 40 °C, 66 kA Icu at 220-440 V AC, IEC 60947-2.","salesMarkdown":"## Selectivity and Coordination Headroom For the site electrical engineer building a selective coordination study: the ENW13212 carries a 50 kA Icw (short-time withstand current for 1 s at 220-440 V AC) and a 75 kA Icm (short-circuit making capacity). The 12 kV Uimp impulse withstand voltage (per IEC 60947-2) confirms insulation coordination at pollution degree 3 (IEC 60664-1) — typical for industrial panels where conductive dust or condensation is present. Maximum breaking time is 35 ms; maximum closing response time is 70 ms. These figures anchor the time-current curve for downstream device coordination. Fixed-mount on a rail base plate, with rear connection and a 70 mm connection pitch without spreader. The 276 mm width × 301 mm height × 196 mm depth footprint fits standard distribution panel compartments. The mechanical durability is 20,000 cycles with maintenance or 10,000 without, per IEC 60947-2; electrical durability is 5,000 cycles at 440 V AC without maintenance.","metaTitle":"Schneider Electric ENW13212 EasyPact NW Circuit Breaker, 125","metaDescription":"Schneider Electric ENW13212 EasyPact NW circuit breaker, 1250 A rated current at 40 °C, 66 kA Icu at 220-440 V AC, IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"196 mm","Range":"EasyPact","Width":"276 mm","title":"ENW13212","Height":"301 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 3 Poles, 1250A, fixed","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW12C","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"1250 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"1250 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e7bf6afdc42d29562414338e8d6a43b0.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW13212/circuit-breaker-frame-adapt-easypact-nw-3-poles-1250a-fixed/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for ENW13212?","answer":"The ENW13212 is sourced and quoted to order against an RFQ through independent distribution; current pricing and availability are confirmed at the time of quote."},{"question":"What is the closest alternative to ENW13212 in the EasyPact NW family?","answer":"Within the EasyPact NW range, the closest alternative would be a different ampere rating or pole configuration in the same ENW12C device short-name family. The ENW13212 is a 3-pole 1250 A variant; a 3-pole 1600 A or 4-pole variant would be the natural cross-reference for a BOM change, but pin compatibility depends on mounting and connection pitch — verify the specific order code against your panel layout."},{"question":"What is ENW13212's listed depth?","answer":"The ENW13212 has a depth of 196 mm."},{"question":"What is ENW13212's listed range?","answer":"The ENW13212 belongs to the EasyPact NW range (product range EasyPact, sub-range EasyPact NW)."},{"question":"What compliance documentation does this brand provide for ENW13212?","answer":"The ENW13212 is certified to IEC 60947-2 and carries a suitability-for-isolation marking per that standard. The datasheet confirms pollution degree 3 per IEC 60664-1. For RoHS, REACH, and UL documentation, refer to the manufacturer's compliance declarations — these are not detailed in the available spec record."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13212","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13212 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}