{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13217","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13217","canonicalUrl":"https://aoctrl.com/schneider/ENW13217","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13217","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW13217, 4P drawout circuit breaker, 630 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2.","salesMarkdown":"The ENW13217 is a 4-pole drawout circuit breaker from the Schneider Electric EasyPact NW range, rated 630 A at 40 °C and built to IEC 60947-2 for distribution duty. The 66 kA Icu at 220...440 V AC 50/60 Hz is the ultimate breaking capacity — the maximum fault current it can safely interrupt once. The 55 kA Ics service breaking capacity is the figure that matters for repeated fault clearing: it can break and then be reclosed without inspection, which is the real-world requirement for a main breaker in an industrial distribution panel. The 50 kA Icw for 1 second tells you it withstands short-time fault current for coordination with downstream devices — essential for selective tripping in a multi-level system. Rated insulation voltage is 1000 V AC, and impulse withstand is 12 kV — this breaker is designed for 440 V AC operational voltage but with headroom for systems where transient overvoltages are common. The IP30 enclosure protection is typical for a drawout breaker mounted inside a switchgear cubicle — not for outdoor or washdown locations. Drawout mounting on a rail base plate — the breaker chassis slides into a fixed cradle, allowing safe isolation without unbolting power cables. Connection pitch is 70 mm without spreader, rear-connected, with horizontal and vertical orientation options. Neutral position is left. Dimensions: 358 mm wide, 322 mm high, 277 mm deep. The 4P 3d protected poles configuration means three poles have thermal-magnetic protection and the fourth (neutral) is switched but not protected — verify your system's neutral earthing arrangement before specifying.","metaTitle":"Schneider Electric ENW13217 EasyPact NW Circuit Breaker, 630","metaDescription":"Schneider Electric ENW13217 EasyPact NW 4P drawout circuit breaker, 630 A rated current, 66 kA Icu at 440 V AC, IEC 60947-2. Currently in production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"277 mm","Range":"EasyPact","Width":"358 mm","title":"ENW13217","Height":"322 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 4 Poles, 630A, withdrawal","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW06C","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","[In] rated current":"630 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"630 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"4P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cc17773beb989308298d0433c6a2dc19.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13217/circuit-breaker-frame-adapt-easypact-nw-4-poles-630a-withdrawal/"},"ai":{"faq":[{"question":"Where can I buy ENW13217 and how do I get a price?","answer":"The ENW13217 is sourced to order against an RFQ through independent distribution. Submit a request with your quantity and target delivery date; availability and current pricing are confirmed at quote time."},{"question":"What is ENW13217's listed depth?","answer":"The ENW13217 has a depth of 277 mm."},{"question":"What is ENW13217's listed range?","answer":"The ENW13217 belongs to the Schneider Electric EasyPact range, specifically the EasyPact NW series."},{"question":"What compliance documentation does this brand provide for ENW13217?","answer":"The ENW13217 is certified to IEC 60947-2 and carries a pollution degree 3 rating per IEC 60664-1. It is suitable for isolation per IEC 60947-2. Specific RoHS, REACH, or UL documentation should be confirmed at quote time from the supplier."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13217","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13217 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}