{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13219","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13219","canonicalUrl":"https://aoctrl.com/schneider/ENW13219","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13219","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, circuit breaker, ENW13219, 1000 A, 66 kA Icu at 440 V AC, 4P drawout.","salesMarkdown":"The ENW13219 is a 1000 A drawout circuit breaker from the EasyPact NW range, built for distribution duty on 440 V AC networks. For selectivity studies, the rated short-time withstand (Icw) is 50 kA for 1 s — it holds closed under that current long enough for a downstream device to clear. Rated operational voltage is 440 V AC, insulation voltage 1000 V AC, and impulse withstand 12 kV — all conforming to IEC 60947-2. The 4-pole version (4P, neutral left) protects all three phases plus neutral with 3d protection on the poles. ## Drawout mounting and panel integration Drawout mounting means the breaker slides into a fixed cradle — you can rack it out for maintenance or replacement without disconnecting the main power cables. Mounting support is a rail base plate; connection pitch is 70 mm without spreader. Rear connection, horizontal or vertical orientation. The 358 mm width, 322 mm height, and 277 mm depth fit standard switchgear cubicle footprints. IP30 protection covers the enclosure — suitable for indoor panel installation, not washdown.","metaTitle":"Schneider Electric ENW13219 EasyPact NW Circuit Breaker, 100","metaDescription":"ENW13219 EasyPact NW circuit breaker, 1000 A, 66 kA Icu at 440 V AC, IEC 60947-2. Drawout mount, 4P, IP30. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"277 mm","Width":"358 mm","Height":"322 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP30","Application":"Distribution","Product Status":"Active","Terminal Pitch":"70 mm without spreader","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category B","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7408319c38ca9a824d05100b4182a118.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13219/circuit-breaker-frame-adapt-easypact-nw-4-poles-1000a-withdrawal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13219/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13219","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13219 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}