{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13220","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13220","canonicalUrl":"https://aoctrl.com/schneider/ENW13220","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13220","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, circuit breaker, ENW13220, 4P, 1250 A at 40 °C, 66 kA Icu at 440 V AC, drawout mounting, IEC 60947-2.","salesMarkdown":"The Schneider Electric ENW13220 is a 4-pole EasyPact NW drawout circuit breaker rated 1250 A at 40 °C, built for distribution duty per IEC 60947-2. The 55 kA Ics service rating tells you it can reclose after a fault at that level without maintenance, which matters on a continuous process line where a nuisance trip can't turn into a shift-long outage. ## Drawout mounting and panel integration Drawout mounting means the breaker chassis stays wired to the bus; the moving portion slides out for inspection or swap without disturbing the rear connections. The 70 mm connection pitch without spreader and rear horizontal/vertical connection positions give the panel builder options for busbar routing. Mounts on a rail base plate. IP30 is standard for enclosed switchgear — not for open panel fronts, but fine behind a door. The 1250 A frame is the continuous current at 40 °C — size your bus and lugs for that, not less. The 66 kA Icu is the ultimate breaking capacity; the 55 kA Ics is the service rating after a fault. The 50 kA Icw for 1 second is the short-time withstand — critical for selective coordination downstream.","metaTitle":"Schneider Electric ENW13220 EasyPact NW Circuit Breaker, 125","metaDescription":"Schneider Electric ENW13220 EasyPact NW 4P circuit breaker, 1250 A rated current, 66 kA Icu at 440 V AC, IEC 60947-2. Drawout mounting. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"277 mm","Range":"EasyPact","Width":"358 mm","Height":"322 mm","Standards":"IEC 60947-2","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW12C","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","[In] rated current":"1250 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"1250 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"4P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/324c9b3ebe604bca9a3e9ab160cbe888.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW13220/circuit-breaker-frame-adapt-easypact-nw-4-poles-1250a-withdrawal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13220/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of ENW13220?","answer":"66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2, with a 55 kA Ics service rating at the same voltage."},{"question":"Where can I buy ENW13220 and how is it quoted?","answer":"Sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing confirmed at quote time."},{"question":"What compliance standards does ENW13220 meet?","answer":"Designed and tested to IEC 60947-2, with suitability for isolation and pollution degree 3 per IEC 60664-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13220","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13220 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}