{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13225","canonicalUrl":"https://aoctrl.com/schneider/ENW13225","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW series, ENW13225, 4P fixed-mount circuit breaker, 630 A rated current, 66 kA Icu breaking capacity at 440 V AC, IEC 60947-2.","salesMarkdown":"For a distribution panel feeding motor control centers or a main switchboard, this breaker gives you Category B utilisation — meaning it's designed for selectivity coordination downstream, not just cable protection. Mounting support is a rail base plate — not a standard DIN rail. The 70 mm connection pitch without spreader means you need matching busbar or cable lugs at that spacing. Rear connection location: plan your cable entry and bending radius behind the panel. The neutral pole is fixed on the left; verify your system's neutral phasing before wiring. Electrical durability is 5,000 cycles at 440 V AC without maintenance under Category B. That's typical for a distribution breaker that sees infrequent switching — not a motor-starting duty cycle. The 35 ms maximum breaking time and 70 ms maximum closing time are the mechanical stroke limits, not the arc-extinction time. The 4P 3d protected poles description means three poles have thermal-magnetic protection; the fourth pole (neutral) is switched but not protected. Verify your system's neutral protection requirements.","metaTitle":"Schneider EasyPact NW ENW13225 Circuit Breaker, 630 A, 66 kA","metaDescription":"Schneider EasyPact NW ENW13225 4P circuit breaker, 630 A rated at 40 °C, 66 kA Icu breaking capacity at 440 V AC. IEC 60947-2. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"196 mm","Range":"EasyPact","Width":"346 mm","title":"ENW13225","Height":"301 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 4 Poles, 630A, fixed","Network type":"AC","Mounting mode":"Fixed","Product weight":"18 kg","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW06C","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","[In] rated current":"630 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"35 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"C","Location of connection":"Rear","IP degree of protection":"IP30","Circuit breaker CT rating":"630 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"4P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"75 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e4fd817869669600cd9e6009289e847.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13225/circuit-breaker-frame-adapt-easypact-nw-4-poles-630a-fixed/"},"ai":{"faq":[{"question":"What is the breaking capacity of ENW13225?","answer":"66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2, with a service breaking capacity (Ics) of 55 kA at the same voltage range."},{"question":"What standards does ENW13225 comply with?","answer":"It complies with IEC 60947-2 for circuit breakers, including pollution degree 3 per IEC 60664-1 and suitability for isolation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}