{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13225","canonicalUrl":"https://aoctrl.com/schneider/ENW13225","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW series, ENW13225, 4P fixed-mount circuit breaker, 630 A rated current, 66 kA Icu breaking capacity at 440 V AC, IEC 60947-2.","salesMarkdown":"For a distribution panel feeding motor control centers or a main switchboard, this breaker gives you Category B utilisation — meaning it's designed for selectivity coordination downstream, not just cable protection. Mounting support is a rail base plate — not a standard DIN rail. The 70 mm connection pitch without spreader means you need matching busbar or cable lugs at that spacing. Rear connection location: plan your cable entry and bending radius behind the panel. The neutral pole is fixed on the left; verify your system's neutral phasing before wiring. Electrical durability is 5,000 cycles at 440 V AC without maintenance under Category B. That's typical for a distribution breaker that sees infrequent switching — not a motor-starting duty cycle. The 35 ms maximum breaking time and 70 ms maximum closing time are the mechanical stroke limits, not the arc-extinction time. The 4P 3d protected poles description means three poles have thermal-magnetic protection; the fourth pole (neutral) is switched but not protected. Verify your system's neutral protection requirements.","metaTitle":"Schneider EasyPact NW ENW13225 Circuit Breaker, 630 A, 66 kA","metaDescription":"Schneider EasyPact NW ENW13225 4P circuit breaker, 630 A rated at 40 °C, 66 kA Icu breaking capacity at 440 V AC. IEC 60947-2. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"196 mm","Width":"346 mm","Height":"301 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP30","Application":"Distribution","Product Status":"Active","Terminal Pitch":"70 mm without spreader","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category B","Mechanical Life Cycles":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e4fd817869669600cd9e6009289e847.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13225/circuit-breaker-frame-adapt-easypact-nw-4-poles-630a-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13225/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}