{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13229","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13229","canonicalUrl":"https://aoctrl.com/schneider/ENW13229","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13229","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, air circuit breaker, ENW13229, 4P, 1600 A at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2, IP30, fixed mounting.","salesMarkdown":"The ENW13229 is a 4-pole air circuit breaker from the EasyPact NW range, rated 1600 A at 40 °C. For selectivity coordination downstream, the Ics (service breaking capacity) is 55 kA at the same voltage — that's the level it can break and still be reused without maintenance. The 50 kA Icw for 1 second tells you the short-time withstand for delayed tripping, critical for zone-selective interlocking. Mounting is fixed on a rail base plate, with rear connections and a 70 mm connection pitch without spreader.","metaTitle":"Schneider EasyPact NW ENW13229 Circuit Breaker, 1600 A, 66 k","metaDescription":"Schneider Electric ENW13229 EasyPact NW air circuit breaker, 1600 A rated current, 66 kA Icu at 440 V, IEC 60947-2. Currently in production. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"196 mm","Width":"346 mm","Height":"301 mm","Voltage":"440 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP30","Application":"Distribution","Product Status":"Active","Terminal Pitch":"70 mm without spreader","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category B","Mechanical Life Cycles":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/029765861097b2d55d873118d4351f43.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW13229/circuit-breaker-frame-adapt-easypact-nw-4-poles-1600a-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW13229/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13229","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13229 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}