{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13269","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13269","canonicalUrl":"https://aoctrl.com/schneider/ENW13269","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13269","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, switch disconnector, ENW13269, 3 poles, 1600 A AC-23A, drawout, 1000 V insulation, 50 kA Icw.","salesMarkdown":"The ENW13269 is a 3-pole switch disconnector from the Schneider Electric EasyPact NW range, rated 1600 A in AC-23A utilization category at 440 V AC — that's the heavy motor-switching duty class, so it handles the high inrush of starting motors and other inductive loads without welding contacts. It's a drawout unit, meaning the switching element slides out of its cradle for safe inspection or replacement without disturbing the main bus connections — a real time-saver in switchgear where uptime matters. Rated insulation voltage is 1000 V AC, with an impulse withstand of 12 kV and a short-time withstand of 50 kA for 1 second, so it's built for distribution panels where fault levels are substantial. It's certified as suitable for isolation per IEC 60947-3, meaning you can safely use it as a visible-break disconnecting means for lockout/tagout procedures. Mounts on a rail base plate in drawout configuration — the 70 mm connection pitch without spreader matches standard busbar centers, and the rear connection location keeps cabling clean in a fixed-cradle setup. Dimensions are 322 mm high, 288 mm wide, 277 mm deep — factor that depth into your enclosure clearance, especially with the drawout rail travel.","metaTitle":"ENW13269 EasyPact NW Switch Disconnector, 1600 A, 3P","metaDescription":"ENW13269 EasyPact NW 3-pole switch disconnector, 1600 A AC-23A, 1000 V insulation, 50 kA short-time withstand. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"277 mm","Range":"EasyPact","Width":"288 mm","title":"ENW13269","Height":"322 mm","Standards":"IEC 60947-3","description":"switch disconnector, EasyPact NW, 3 Poles, 1600A, AC, withdrawable","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW16CA","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","Connection position":"Vertical Horizontal","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Breaking capacity code":"CA","Location of connection":"Rear","IP degree of protection":"IP30","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 1600 A AC 50/60 Hz 440 V","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"50 kA during 1 s conforming to IEC 60947-3 at 220...440 V","[Icm] rated short-circuit making capacity":"75 kA 220...440 V AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6bf6c7d954831eef926dcedb5089a19b.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW13269/switch-disconnector-easypact-nw-3-poles-1600a-ac-withdrawable/"},"ai":{"faq":[{"question":"What is the rated operational current of ENW13269?","answer":"The ENW13269 is rated 1600 A in AC-23A duty at 440 V AC, 50/60 Hz per IEC 60947-3."},{"question":"What compliance documentation does this brand provide for ENW13269?","answer":"The ENW13269 is certified to IEC 60947-3 for switch-disconnector performance and isolation suitability, with a rated insulation voltage of 1000 V AC and pollution degree 3 per IEC 60664-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13269","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13269 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}