{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW13286","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW13286","canonicalUrl":"https://aoctrl.com/schneider/ENW13286","factsUrl":"https://aoctrl.com/api/mcp/products/ENW13286","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW series, ENW13286 switch disconnector, 1250 A, 3 poles, AC-23A, 440 V AC, fixed mounting, rear connection.","salesMarkdown":"## Switch disconnector for distribution — 1250 A, AC-23A duty The Schneider Electric ENW13286 is a 3-pole switch disconnector from the EasyPact NW range, rated 1250 A operational current in AC-23A utilisation category at 440 V AC. It is certified for isolation per IEC 60947-3, meaning it provides visible-break isolation when the contact position indicator shows open. ## Mounting and connection — fixed base plate, rear terminals Fixed mounting on a rail base plate. Connection pitch is 70 mm without spreader, and the rear-located terminals accept vertical or horizontal cable entry. Dimensions are 346 mm wide × 301 mm high × 196 mm deep — check the gland-plate layout before cutting the back panel. IP30 protection keeps fingers out but expects a cabinet door. ## Withstand and making capacity — fault-current handling Rated short-time withstand current (Icw) is 50 kA for 1 second at 220–440 V — that is the current the switch can carry without damage during a fault while the upstream breaker clears. Rated short-circuit making capacity (Icm) is 75 kA at the same voltage. Insulation voltage (Ui) is 1000 V AC, so the switch can sit on a 690 V bus without derating the insulation system.","metaTitle":"ENW13286 EasyPact NW Switch Disconnector, 1250 A, 3P","metaDescription":"ENW13286 EasyPact NW switch disconnector, 1250 A rated operational current, 3 poles, AC-23A, IEC 60947-3. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"196 mm","Range":"EasyPact","Width":"346 mm","title":"ENW13286","Height":"301 mm","Standards":"IEC 60947-3","description":"switch disconnector, EasyPact NW, 1250A, 4 Poles, Fixed","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"70 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"3 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW12CA","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","Connection position":"Vertical Horizontal","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Breaking capacity code":"CA","Location of connection":"Rear","IP degree of protection":"IP30","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 1250 A AC 50/60 Hz 440 V","[Ue] rated operational voltage":"440 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"50 kA during 1 s conforming to IEC 60947-3 at 220...440 V","[Icm] rated short-circuit making capacity":"75 kA 220...440 V AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b6020b08ea225159de676bd67a9dc202.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW13286/switch-disconnector-easypact-nw-1250a-4-poles-fixed/"},"ai":{"faq":[{"question":"What is the rated operational current of ENW13286?","answer":"1250 A in AC-23A utilisation category at 440 V AC, 50/60 Hz, per IEC 60947-3. The AC-23A rating means it is suited for switching motor loads and other highly inductive circuits, not just resistive loads."},{"question":"What standards does ENW13286 comply with?","answer":"IEC 60947-3 for switch-disconnectors, including isolation suitability. Rated insulation voltage 1000 V AC, impulse withstand 12 kV, pollution degree 3 per IEC 60664-1."},{"question":"Where can I buy ENW13286 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — no stock figures or prices are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW13286","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW13286 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}