{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW15563","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW15563","canonicalUrl":"https://aoctrl.com/schneider/ENW15563","factsUrl":"https://aoctrl.com/api/mcp/products/ENW15563","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, Trip System 5.0, control unit, 630-6300 A, 690 V AC, LSI protection, drawout and fixed mounting.","salesMarkdown":"The ENW15563 is a microprocessor-based Trip System 5.0 control unit for the Schneider Electric EasyPact NW range of air circuit breakers. It's rated for standard industrial applications on AC networks at 50/60 Hz, with a trip unit rating spanning 630 to 6300 A and a rated operational voltage of 690 V AC conforming to IEC 60947-2. The failure mode this unit addresses is the protection coordination of a large industrial feeder. The LSI protection profile — long-time (L), short-time (S), and instantaneous (I) — means you can shape the trip curve to the load's inrush and the downstream branch's fault-clearing capability. The thermal memory function prevents reclosure into a still-hot conductor, which is the kind of detail that matters when you're coordinating a multi-level distribution system and don't want nuisance trips on a reclose after a transient fault. ## Protection curve and adjustability The long-time pickup (Ir) is adjustable across 10 settings from 0.4 to 1.0 x In, with a corresponding long-time delay (Tr) adjustable from 0.5 to 24 seconds at 6 x Ir, accuracy 0 to -20%. This gives you the granularity to match the thermal curve of a large motor or a transformer-fed load without oversizing the breaker frame. Short-time pickup (Isd) adjusts across 10 settings from 1.5 to 10 x Ir, with a delay (Tsd) from 100 to 600 ms. The instantaneous pickup (Ii) also has 10 settings, ranging from 2 to 15 x In. That range on the instantaneous band — up to 15x In — is what lets you ride through the inrush of a fully loaded transformer bank while still clearing a bolted fault within one cycle. ## Physical integration and mounting The unit measures 200 mm high, 58 mm wide, and 77 mm deep. It mounts via a fixed drawout mechanism — the control unit slides into the breaker cradle without removing the breaker from the switchgear. The neutral position is on the left side of the assembly. Protected poles can be configured as 3D (three poles protected), 3D + N/2 (three poles plus half-rated neutral), or 4D (four poles protected), with neutral protection settings selectable as Without protection, 0.5 x Ir, or 1 x Ir.","metaTitle":"ENW15563 EasyPact NW Trip System 5.0, 630-6300 A","metaDescription":"Schneider Electric ENW15563 EasyPact NW Trip System 5.0 control unit. Active production. Rated 690 V AC, 630-6300 A, LSI protection. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"77 mm","Width":"58 mm","title":"ENW15563","Height":"200 mm","description":"Trip unit, EasyPact NW, Trip System 5.0, drawout and fixed","Network type":"AC","Mounting mode":"Fixed Drawout","Thermal memory":"Yes","Trip unit name":"Trip System 5.0","Protection type":"Overload protection (long time) Instantaneous short-circuit protection Short time short-circuit protection","lifecycle_stage":"current","Fault indication":"Overload Short-circuit Internal fault","Neutral position":"Left","Range of product":"EasyPact NW","Trip unit rating":"630...6300 A","Network frequency":"50/60 Hz","Poles description":"3P 4P","Trip unit technology":"Micro-processor based","Product or component type":"Control unit","Neutral protection setting":"Without protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)","Circuit breaker application":"Standard Industrial","Protected poles description":"3D 3D + N/2 4D","Trip unit protection functions":"LSI","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 10 settings","Short-time delay adjustment type":"Adjustable 11 settings","Long time pick-up adjustment range":"0.4...1 x In Off","Ambient air temperature for storage":"-25...85 °C","Long time pick-up adjustment type Ir":"Adjustable 10 settings","Ambient air temperature for operation":"-5...70 °C","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s (6 x Ir), accuracy: 0...- 20 %","Instantaneous pick-up adjustment range":"2...15 x In, accuracy: +/- 10 % Off","Short-time pick-up adjustment type Isd":"Adjustable 10 settings","[Tsd] Short-Time Delay Adjustment Range":"100...600 ms","Instantaneous pick-up adjustment type Ii":"Adjustable 10 settings","[Isd] short-time pick-up adjustment range":"1.5...10 x Ir"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b0645b98862e859eccf1f96a14549abf.pdf","sourceUrl":"https://www.se.com/sa/en/product/ENW15563/trip-unit-easypact-nw-trip-system-5-0-drawout-and-fixed/"},"ai":{"faq":[{"question":"What is ENW15563's trip unit rating range?","answer":"The ENW15563 has a trip unit rating of 630 to 6300 A, covering a wide range of industrial feeder sizes."},{"question":"What protection functions does the Trip System 5.0 offer?","answer":"The Trip System 5.0 provides LSI protection: long-time (overload), short-time, and instantaneous short-circuit protection. It also includes thermal memory and fault indication for overload, short-circuit, and internal fault conditions."},{"question":"Where can I buy ENW15563 and how is it quoted?","answer":"The ENW15563 is sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quotation through independent distribution channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW15563","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW15563 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}