{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW225H3MW6SVG","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW225H3MW6SVG","canonicalUrl":"https://aoctrl.com/schneider/ENW225H3MW6SVG","factsUrl":"https://aoctrl.com/api/mcp/products/ENW225H3MW6SVG","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact ENW225H3MW6SVG, 3-pole drawout circuit breaker, 2500 A, 66 kA Icu at 440 V AC, Trip System 6.0s LSIG.","salesMarkdown":"## EasyPact ENW225H3MW6SVG — 2500 A Drawout Breaker with LSIG Trip The Schneider Electric ENW225H3MW6SVG is a 3-pole drawout circuit breaker from the EasyPact range, rated at 2500 A continuous (at 50 °C) with a breaking capacity of 66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. It carries the Trip System 6.0s electronic trip unit with LSIG protection — long-time, short-time, instantaneous, and earth-fault — making it a Category B breaker suited for distribution in main switchboards. For a distribution board fed from a transformer in the 2–3 MVA range, that SCCR headroom covers most industrial service-entrance faults without cascading upstream. The LSIG trip unit gives you four independent protection curves: long-time (overload), short-time (selective coordination with downstream breakers), instantaneous (fast clearing for high faults), and earth-fault (ground leakage). The 2500 A CT rating matches the breaker frame, and the current sensor range spans 1000/4000 A, so the same frame can be re-rated downward if needed. Rated insulation voltage (Ui) is 1000 V AC — the breaker is electrically safe at that voltage level, though the operating network here is 440 V. Drawout mounting on a base plate or rail — the breaker chassis slides in and out for maintenance without disturbing the rear-connected power cables. Connection pitch is 115 mm without spreader; vertical or horizontal rear connection gives flexibility in cabinet layout. IP40 protection means it's enclosed against tools and small objects, not washdown. Electrical durability at 440 V AC is 5,000 cycles Category B without maintenance — that's the number to watch for a breaker that sees frequent switching, not just fault protection.","metaTitle":"Schneider Electric ENW225H3MW6SVG EasyPact Circuit Breaker,","metaDescription":"Schneider Electric ENW225H3MW6SVG EasyPact circuit breaker, 2500 A rated current, 66 kA Icu at 440 V AC, IEC 60947-2. LSIG electronic trip unit. Active production. Available to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"441 mm","title":"ENW225H3MW6SVG","Height":"439 mm","Standards":"IEC 60947-2","description":"Circuit breaker, EasyPact NW, 2500A, 66KA, 3 Poles, Trip System 6.0S(without display), Manual Drawout Vertical","Control type":"Manually operated","Network type":"AC","Mounting mode":"Drawout","Trip unit name":"Trip System 6.0s","Protection type":"Short time short-circuit protection Instantaneous short-circuit protection Overload protection (long time) Earth fault","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Fault indication":"Overload Internal fault Earth fault Short-circuit","Mounting support":"Base plate Rail","Pollution degree":"4 conforming to IEC 60664-1","Trip unit rating":"2500 A","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW25H","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"2500 A at 50 °C","Connection position":"Vertical Horizontal","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"H","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"2500 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Current sensor rating range":"1000/4000 A","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 9 settings","Zone selective interlocking ZSI":"With","Short-time delay adjustment type":"Adjustable 5 settings","Long time pick-up adjustment range":"0.4...1 x In","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ground-fault pick-up adjustment type":"Adjustable 9 settings","Long time pick-up adjustment type Ir":"Adjustable 9 settings","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"66 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s at 6 x Ir","Instantaneous pick-up adjustment range":"2...15 x In Off","Short-time pick-up adjustment type Isd":"Adjustable 9 settings","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Tsd] Short-Time Delay Adjustment Range":"100...400 ms","Instantaneous pick-up adjustment type Ii":"Adjustable 9 settings","[Icw] rated short-time withstand current":"66 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] short-time pick-up adjustment range":"1.5...10 x Ir","[Ig] ground-fault pick-up adjustment range":"500...1200 A","Ground-fault time delay adjustment type -tg":"Adjustable 5 settings","[Tg] Ground-Fault Time Delay Adjustment Range":"100...400 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a091c01405bfa344a220b577d5875c9.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW225H3MW6SVG/circuit-breaker-easypact-nw-2500a-66ka-3-poles-trip-system-6-0swithout-display-manual-drawout-vertical/"},"ai":{"faq":[{"question":"What is ENW225H3MW6SVG's breaking capacity?","answer":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2."},{"question":"What protection functions does the Trip System 6.0s provide?","answer":"LSIG protection: long-time overload, short-time short-circuit, instantaneous short-circuit, and earth-fault protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW225H3MW6SVG","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW225H3MW6SVG when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}