{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24101","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24101","canonicalUrl":"https://aoctrl.com/schneider/ENW24101","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24101","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW ENW08N frame, circuit breaker, 3P, 800 A at 40 °C, 50 kA Icu at 440 V AC, drawout mount, IP40.","salesMarkdown":"## What this 800 A drawout breaker does for your main The ENW24101 is a Schneider Electric EasyPact NW circuit breaker on the ENW08N frame — a three-pole, 800 A drawout unit built for distribution duty. That 800 A rating at 40 °C tells you it handles full continuous current in a warm switchroom without derating; push it to 60 °C and you'll need to knock the ampacity down per the thermal curve. ## Drawout mount, rear connection — panel integration Drawout mounting means the breaker slides into a cradle, so you can rack it out for maintenance or replacement without pulling the bus bars. Rear connection keeps the power cables out of the front of the panel — cleaner layout, less clutter for the guy wiring the control transformer. The 115 mm connection pitch without spreader sets the bus spacing; if you're retrofitting into an existing lineup, measure that pitch before ordering the adapter kit. IP40 keeps tools and fingers out but isn't rated for washdown — keep it indoors. ## What the standards and durability numbers mean Compliant with IEC 60947-2, the standard for low-voltage circuit breakers — that's the spec that defines the Icu, Ics, and Icw ratings, so you know the test protocol behind the numbers. Mechanical durability is 20,000 cycles with maintenance, 10,000 without; electrical durability is 6,000 cycles at 440 V without maintenance. That's not a daily-switch duty cycle — it's a main breaker that cycles on fault or maintenance, not a contactor running every minute.","metaTitle":"ENW24101 EasyPact NW Circuit Breaker, 800 A, 50 kA","metaDescription":"Schneider Electric ENW24101 EasyPact NW circuit breaker, 800 A rated current, 50 kA breaking capacity at 440 V AC, IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"395 mm","Width":"441 mm","Height":"439 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Distribution","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm without spreader","Pollution Degree":"4 conforming to IEC 60664-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Utilization Category":"Category B","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-5...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad9d826052fbd34442fb67c549573b46.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24101/circuit-breaker-frame-adapt-easypact-nw-3-poles-800a-n-withdrawal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24101/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24101","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24101 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}