{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24106","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24106","canonicalUrl":"https://aoctrl.com/schneider/ENW24106","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24106","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, circuit breaker, ENW24106, 3P, 2500 A at 40 °C, 50 kA Icu at 440 V AC, drawout mounting.","salesMarkdown":"The ENW24106 is a 3-pole EasyPact NW circuit breaker rated 2500 A at 40 °C, with a breaking capacity of 50 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2. At 690 V the Icu drops to 42 kA, still sufficient for most industrial secondary distribution. The drawout mounting means the breaker chassis slides into a fixed cradle, allowing safe isolation and replacement without unbolting busbars — standard for switchgear lineups where maintenance access matters. Rated insulation voltage (Ui) is 1000 V AC, and the impulse withstand (Uimp) is 12 kV, confirming the part is designed for systems where transient overvoltages are a concern — typical in industrial environments with motor starts and capacitor switching. ## Deployment context This breaker is a drawout unit designed for mounting on a rail in low-voltage switchgear assemblies. The rear connection position with a 115 mm pitch without spreader matches standard busbar take-off spacing in common switchgear cubicles. ## Key approvals and standards Certified to IEC 60947-2 for low-voltage switchgear and controlgear. Suitability for isolation means it can be used as a disconnecting means per code. Electrical durability is 5000 cycles at 440 V and 2500 cycles at 690 V without maintenance; mechanical durability is 20000 cycles with maintenance, 10000 without. These figures guide preventive maintenance scheduling — plan inspection at the 5000-cycle mark for typical 440 V distribution.","metaTitle":"Schneider Electric ENW24106 EasyPact NW Circuit Breaker, 250","metaDescription":"ENW24106 EasyPact NW circuit breaker, 2500 A rated current at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2. Drawout mounting, 3-pole. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"441 mm","title":"ENW24106","Height":"439 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 3 Poles, 2500A, N, withdrawal","Control type":"Push-button","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW25N","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"2500 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"N","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"2500 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1e625122bbeabd14259857dddb9043af.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW24106/circuit-breaker-frame-adapt-easypact-nw-3-poles-2500a-n-withdrawal/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for ENW24106?","answer":"Pricing and availability are confirmed at quote time. Submit an RFQ through this listing; the part is sourced to order through independent distribution."},{"question":"What is ENW24106's rated breaking capacity?","answer":"The ENW24106 has a breaking capacity of 50 kA Icu at 220…440 V AC 50/60 Hz and 42 kA Icu at 690 V AC 50/60 Hz, both conforming to IEC 60947-2."},{"question":"What is the rated current of ENW24106?","answer":"The rated current (In) is 2500 A at 40 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}