{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24107","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24107","canonicalUrl":"https://aoctrl.com/schneider/ENW24107","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24107","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, EasyPact NW, circuit breaker, ENW24107, 3200 A at 40 °C, 50 kA Icu at 440 V AC, 3P, drawout, IP40, IEC 60947-2.","salesMarkdown":"## What this 3200 A drawout breaker is for It's a drawout unit — the breaker chassis stays wired to the bus, and the moving portion pulls out for inspection or swap without killing the main bus. That's the whole point of drawout: you isolate the breaker, rack it out, work on it on the bench, and slide a spare back in. Line-down time measured in minutes, not hours. ## Breaking capacity — what the ratings actually mean The ENW24107 carries a 50 kA Icu (ultimate breaking capacity) at 220…440 V AC, and 42 kA at 690 V AC, both per IEC 60947-2. Icu is the maximum fault the breaker can clear once and still be functional afterward — it's the 'one-shot' rating. For repetitive faults (like a motor starting surge that trips), the Ics (service breaking capacity) is the same 50 kA at 440 V, meaning it can clear that fault level repeatedly without needing replacement. The short-time withstand (Icw) is 50 kA for 1 second at 440 V, which matters for selective coordination downstream — this breaker can sit open while a downstream device clears a lower-level fault, then reclose without damage. Dimensions: 441 mm wide × 439 mm high × 395 mm deep. That's a big breaker — plan for a dedicated compartment in the switchgear lineup, not a DIN-rail mount. It's IP40 rated (finger-safe, not sealed), so indoor switchboard only. Connection is rear-mounted, vertical or horizontal orientation, with a 115 mm pitch without spreader. The control is push-button only; no motor operator or remote trip included as standard. Designed and tested to IEC 60947-2 for low-voltage switchgear and controlgear. Rated insulation voltage 1000 V AC, operational voltage 690 V AC, impulse withstand 12 kV. Electrical durability: 5000 cycles at 440 V without maintenance, 2500 cycles at 690 V. Mechanical: 20000 cycles with maintenance, 10000 without. Maximum breaking time 25 ms, closing response 70 ms.","metaTitle":"Schneider Electric ENW24107 EasyPact NW Circuit Breaker, 320","metaDescription":"Schneider Electric ENW24107 EasyPact NW circuit breaker. 3200 A rated current, 50 kA breaking capacity at 440 V AC. IEC 60947-2, drawout mounting. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"441 mm","title":"ENW24107","Height":"439 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 3 Poles, 3200A, N, withdrawal","Control type":"Push-button","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW32N","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"3200 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"N","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"3200 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/182b7e6bbc55ba59564cce6906ddbd9b.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24107/circuit-breaker-frame-adapt-easypact-nw-3-poles-3200a-n-withdrawal/"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative to ENW24107 in this component family?","answer":"Within the EasyPact NW family, the closest alternative is the ENW32N, which shares the same 3200 A frame and drawout mounting. The ENW24107 is the specific order code for the push-button-controlled variant; verify control voltage and accessory fit before substituting."},{"question":"What is ENW24107's listed depth (395 mm) on this component line?","answer":"The ENW24107 has a depth of 395 mm. That's the dimension from the rear connection face to the front of the breaker — critical for switchgear compartment depth planning."},{"question":"What compliance documentation does this brand provide for ENW24107?","answer":"The ENW24107 is designed to IEC 60947-2 for circuit breakers. It carries an insulation voltage rating of 1000 V AC and impulse withstand of 12 kV. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration of conformity with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24107","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24107 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}